GE EPM 5200, EPM 5300, EPM 5350 Group 4 Programming Format for Limit Condition, Group 4 Functions

Models: EPM 5300 EPM 5200 EPM 5350

1 134
Download 134 pages 15.43 Kb
Page 105
Image 105

CHAPTER 12: GROUPS 4, 5 AND 6—SET LIMITS AND RELAYS

GROUP 4: PROGRAMMING FORMAT FOR LIMIT CONDITION

12.4 Group 4: Programming Format for Limit Condition

Table 12–1: Group 4 Programming Format

Group and Function Number

Function

 

 

40.

LM1/LM2 Set Limits for Volts AN, BN, CN

 

 

41.

LM1/LM2 Set Limits for Volts AB, BC, CA

 

 

42.

LM1/LM2 Set Limits for Amps A, B, C

 

 

43.

LM1/LM2 Set Limits for Amps Neutral

 

 

4E.

Exit Programming GROUP 4

 

 

These functions have a two-part entry:

Part 1:

The first switch sets the limit to trip either above or below the Limit Value.

The second switch sets whether Relay 1 will trip when the condition occurs.

The third switch sets whether Relay 2 will trip when the condition occurs.

Part 2:

The second part is the Limit Value.

Table 12–2: Group 4: Functions 0–3

 

LM1

LM2

Above/below

Relay 1

 

Relay 2

 

Value

 

LED

LED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

OFF

Digit Up-trigger above value

Digit Up-enabled

 

Digit Up-enabled

0-9999

 

Digit Down-trigger below value

Digit Down-disabled

 

Digit Down-disabled

0-9999

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

ON

Digit Up-trigger above value

Digit Up-enabled

 

Digit Up-enabled

0-9999

 

Digit Down-trigger below value

Digit Down-disabled

 

Digit Down-disabled

0-9999

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 12–3: Group 4: Example for Function 0

 

 

 

 

 

 

 

 

 

 

 

 

LM1

LM2

Above/below

Relay 1

 

Relay 2

 

Value

 

LED

LED

 

 

 

 

 

 

 

 

 

 

ON

OFF

Digit Up

Digit Up

 

Digit Down

 

0135

 

 

 

 

 

 

 

 

 

 

OFF

ON

Digit Down

Digit Down

 

Digit Up

 

0090

 

 

 

 

 

 

 

 

 

EXAMPLE: If voltages exceed 135 V, LM1 is triggered and Relay 1 is enabled. If the voltages fall below 90 V, LM2 is triggered and Relay 2 is enabled.

EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL

12–93