GROUP 1, FUNCTION 2

CHAPTER 10: PROGRAMMING GROUP 1 – VOLTAGE, AMP AND WATT SCALE SETTINGS

To change the scale factor setting for wattage:

Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

MAX

AC VOLTS

A B C A B C

MIN

N N N B C A

LM1

 

LM2

AC AMPS

 

 

A B C N

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KVA

 

 

 

 

 

 

KVAH

 

 

KWH

 

 

FREQ

 

KVAR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX/MIN

 

VOLTS

 

 

AMPS

 

POWER

 

PHASE

 

 

 

 

 

 

 

 

LIMITS

 

 

 

 

 

 

 

 

 

NEXT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX

AC VOLTS

A B C A B C

MIN

N N N B C A

LM1

 

LM2

AC AMPS

 

 

A B C N

 

POWER

PF

KW

KVAH

KWH

 

FREQ

KVA

 

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

NEXT

 

Step 1:

a. Enter Group Level of Programming Mode (see Chp. 8). b. Press MAX/MIN/LIMITS until 1. appears in upper

display.

Step 2:

a. Press AMPS to activate the Group.

b. Press MAX/MIN/LIMITS until 12. appears in upper display.

Middle display indicates current Scale Factor Setting.

Lower display indicates 9999 (including current decimal placement).

10–80

EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL