GROUP 0, FUNCTION 6—KYZ PARAMETER SELECTION

CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP

SITUATION 3: FSW=99.99

Selection is Multiply by 20

This means that every .0005 unit WH=1 pulse.

Unit=Kilo (see Group 1, Function 2)

Result: For every 1 KWH increment on the counter, the meter will output 2,000 pulses.

SITUATION 4: FSW=9.999

Selection is Multiply by 20

Unit=Kilo (see Group 1, Function 2)

This means that every .00005 WH=1 pulse.

Result: For every 1 KWH increment on the counter, the meter will output 20,000 pulses.

9.8.2How to Use KYZ Pulse Value Table for Division:

SITUATION 1: FSW=9999.

Selection is Divide by 10

This means that every 10 unit WH=1 pulse.

Unit=Kilo (see Group 1, Function 2)

Result: For every 10 KWH increment on the counter, the meter will output 1 pulse.

SITUATION 3: FSW=99.99

Selection is Divide by 20

This means that every .2 unit WH=1 pulse.

Unit=Kilo (see Group 1, Function 2)

Result: For every 1 KWH increment on the counter, the meter will output 5 pulses.

SITUATION 2: FSW=999.9

Selection is Divide by 10

This means that every 1 unit WH=1 pulse.

Unit=Kilo (see Group 1, Function 2)

Result: For every 1 KWH increment on the counter, the meter will output 1 pulse.

SITUATION 4: FSW=9.999

Selection is Divide by 20

Unit=Kilo (see Group 1, Function 2)

This means that every .02 WH=1 pulse.

Result: For every 1 KWH increment on the counter, the meter will output 50 pulses.