GE EPM 5300, EPM 5200, EPM 5350 instruction manual Open Delta System Installation Programming

Models: EPM 5300 EPM 5200 EPM 5350

1 134
Download 134 pages 15.43 Kb
Page 70
Image 70

GROUP 0, FUNCTION 3 — SYSTEM CONFIGURATIONCHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP

 

a

Non-significant will blank leading zero

UP: Enable

 

DOWN: Disable

 

 

 

 

 

 

 

 

b

Reset Protection

UP: Enable

 

(see Part I: Installation and Operation)

DOWN: Disable

1

 

 

 

 

c

Phase Reversal Rotation Selection

UP: CBA Rotation

 

 

DOWN: ABC Rotation

 

 

 

 

 

 

 

 

d

Open Delta Installation

UP: Enable

 

(see Part I: Installation and Operation)

DOWN: Disable

 

 

 

 

 

 

 

a

Limit/Relay Control

UP: Average

 

DOWN: Instantaneous

 

 

 

 

 

 

 

 

 

Power Factor Polarity Indicates +

UP: -PF

 

b

(voltage referenced) or

 

DOWN: +PF

2

 

- (current referenced)

 

 

 

 

 

 

 

 

For EI-BUS protocol: Switch C is DOWN, Switch D is DOWN.

 

c, d

For MODBUS protocol, ASCII framing: Switch C is UP, Switch D is UP.

 

For MODBUS protocol, RTU framing: Switch C is DOWN Switch D is UP.

 

 

 

 

For DNP 3.0 protocol: Switch C is UP, Switch D is DOWN.

 

 

 

 

 

 

Trip Relay Computer Control 1

UP: Enable

 

a

(Relay Control 1 and 2 apply only if Relay

 

DOWN: Disable

 

 

Option -NL was ordered.)

 

 

 

 

 

 

 

 

 

Trip Relay Computer Control 2

UP: Enable

 

b

(Relay Control 1 and 2 apply only if Relay

 

DOWN: Disable

 

 

Option -NL was ordered.)

 

 

 

 

 

 

 

 

 

 

UP: Enable

3

c

RS-232 or RS-485 Communications or

Communications

Print

DOWN: Enable DC

 

 

 

 

 

Output

 

 

 

 

 

 

DC Output

UP: Enable DC Output or

 

 

(To operate DC Output, disable PACK 3,

 

 

Switch C)

Print Communication

 

d

or

DOWN: Disable DC

 

 

Print Operating and Programming Data

 

 

(To print, set PACK 3 Switches C and D to

Output and Print

 

 

UP position.)

 

 

 

 

 

9.3.1Open Delta System Installation Programming

A special switch is used to indicate that the electrical system being monitored is a Three- phase WYE or Three-Wire Open Delta System using the connection installation (see Chapter 3). The switch is located in GROUP 0, FUNCTION 3, Pack 1, Switch D.

This switch should be set to UP only if the electrical system is a Three-Wire Delta or Open Delta, using 2 PTs. Otherwise, the switch should be set to DOWN. Failure to select this switch results in Phase-to-Neutral readings, as well as incorrect power readings, with the 2PT connection.

Special Open Delta Connection Installation should be followed in the Installation and

Operation section (Chapter 3).

9–58

EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL

Page 70
Image 70
GE EPM 5300, EPM 5200, EPM 5350 instruction manual Open Delta System Installation Programming