CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP

GROUP 0, FUNCTION 0—THE INTEGRATION INTERVAL

METER ADDRESS: Identifies the meter when communicating with digital communications. When numerous meters are at one site, it is essential that each meter have its own address. Otherwise, all meters speak at the same time and communication is useless.

To change the Meter Address:

Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

MAX

AC VOLTS

A B C A B C

MIN

N N N B C A

LM1

 

LM2

AC AMPS

 

 

A B C N

 

POWER

 

 

 

PF

 

 

 

KW

 

 

 

KVA

KVAH

KWH

FREQ

KVAR

MAX/MIN

VOLTS AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 1:

a. Enter Group Level of Programming Mode (see Chp. 8).

b. Press MAX/MIN/LIMITS until 0. appears. c. Press AMPS to activate the Group.

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 3:

a. Press AMPS once to begin Data Entry Sequence.

The previous value shifts to middle display and four dashes appear in lower display.

b. Press VOLTS for desired number. c. Press AMPS to store each digit.

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 2:

a. Press MAX/MIN/LIMITS until Function 01. appears in upper display.

Lower display indicates the current Meter Address.

MAX

 

 

AC VOLTS

 

 

A

B C A B C

MIN

 

 

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Repeat this procedure until new Address is entered.

When complete, middle display blanks and lower display indicates new Address.

See Chapter 14 to Exit.

EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL

9–55

Page 67
Image 67
GE EPM 5300, EPM 5200, EPM 5350 instruction manual To change the Meter Address, Programming Group 0 Global Meter Setup