LIMITS OR RELAYS PROGRAMMING PROCEDURE

CHAPTER 12: GROUPS 4, 5 AND 6—SET LIMITS AND RELAYS

12.8 Limits or Relays Programming Procedure

The procedure for programming any limit or relay for each group is identical. The example below signifies the exact procedure for programming a Limit/Relay for GROUPS 4–6.

—Group 4 is used as an example.

Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

GROUP

MAX

AC VOLTS

MAX

AC VOLTS

A B C A B

C

A B C A B C

MIN

N N N B C A

MIN

 

LM1

N N N B C A

 

 

 

LM1

 

LM2

 

 

 

AC AMPS

 

LM2

AC AMPS

 

 

 

 

 

 

A B C N

 

 

A B C N

 

 

 

 

 

POWER

 

POWER

 

 

 

 

 

 

PF

LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PF

 

 

 

 

 

 

KW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

 

 

 

 

 

 

KVA

VALUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KVA

KVAH

 

KWH

 

FREQ

 

KVAR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KVAH

 

 

KWH

 

 

 

FREQ

 

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

NEXT

LIMITS

 

 

NEXT

FUNCTION

RELAY SWITCHES

Step 1:

a. Enter Group Level of Programming Mode

(see Chp. 8).

b. Press MAX/MIN/LIMITS until 4. appears in upper display.

c. Press AMPS to activate the Group.

Step 2:

a. Press MAX/MIN/LIMITS to select desired Function.

Middle display provides the currently selected value for whether to trip above or below, activate Relay 1 and activate Relay 2.

Left Switch: UP position indicates above tripping value for lower display’s value. DOWN position indicates below tripping.

Middle Switch: UP position sets Relay 1 to trip.

DOWN position doesn’t activate Relay 1 when limit condition exists.

Right Switch: Same as Middle Switch , regarding Relay 2.

b. Press VOLTS to toggle between LM1 and LM2 settings.

The LM1 or LM2 annunciator indicates the limit being displayed.

12–98