CHAPTER 11: PROGRAMMING GROUP 2 - METER CALIBRATION

GROUP 2, FUNCTIONS 0–2

11.2Group 2, Functions 0–2

-HIGH END CALIBRATION OF VOLTAGE CHANNELS, HIGH AND LOW END CALIBRATION OF AMPERAGE CHANNELS -

To change the calibration (high end—Functions 0 and 1):

Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 1:

a. Enter Group Level of Programming Mode (see Chp. 8).

b. Press MAX/MIN/LIMITS until 2. appears in upper display.

c. Press AMPS to activate the Group.

A one-digit password is required to continue.

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 2:

Refer to Table 11-1for Function Number that corresponds to the area requiring calibration. Calibration for each area begins with A and then moves to B and C.

a. Press MAX/MIN/LIMITS to change Function number.

d.Press VOLTS until 5 appears.

e.Press AMPS to select.

EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL

11–85

Page 97