CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP

GROUP 0, FUNCTION 6—KYZ PARAMETER SELECTION

MAX

 

 

AC VOLTS

 

 

A

B C A B C

MIN

 

 

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Applies to -NL2 Option only:

Step 5:

a. Press VOLTS to proceed to another port (06.1 or 06.2). Repeat this procedure to change parameters.

See Chapter 14 to Exit.

Table 9–2: KYZ Pulse Value

Selection

KYZ PULSE VALUE per

KYZ PULSE VALUE per

KYZ PULSE VALUE

KYZ PULSE VALUE per

Watt HOUR

Watt HOUR

per Watt HOUR

Watt HOUR

in 06P

FSW=9999.

FSW=999.9

FSW=99.99

FSW=9.999

 

 

 

 

 

 

Multiply by 1

1.0 unit WH

0.1 unit WH

0.01 unit WH

0.001 unit WH

 

 

 

 

 

Multiply by 2

0.5 unit WH

0.05 unit WH

0.005 unit WH

0.0005 unit WH

 

 

 

 

 

Multiply by 10

0.1 unit WH

0.01 unit WH

0.001 unit WH

0.0001 unit WH

 

 

 

 

 

Multiply by 20

0.05 unit WH

0.005 unit WH

0.0005 unit WH

0.00005 unit WH

 

 

 

 

 

Divide by 1

1.0 unit WH

0.1 unit WH

0.01 unit WH

0.001 unit WH

 

 

 

 

 

Divide by 2

2.0 unit WH

0.2 unit WH

0.02 unit WH

0.002 unit WH

 

 

 

 

 

Divide by 10

10.0 unit WH

1.0 unit WH

0.1 unit WH

0.01 unit WH

 

 

 

 

 

Divide by 20

20.0 unit WH

2.0 unit WH

0.2 unit WH

0.02 unit WH

 

 

 

 

 

The unit WH refers to the counter value on the meter, where the unit equals Kilo or Mega user-defined.

The FSW number is used only for decimal point placement (see Chapter 10).

9.8.1How to Use KYZ Pulse Value Table for Multiplication:

SITUATION 1: FSW=9999.

Selection is Multiply by 2

This means that every .5 unit WH =1 pulse.

Unit=Kilo (see Group 1, Function 2)

Result: For every 1 KWH increment on the counter, the meter will output 2 pulses.

SITUATION 2: FSW=999.9

Selection is Multiply by 2

This means that every .05 unit WH=1 pulse.

Unit=Kilo (see Group 1, Function 2)

Result: For every 1 KWH increment on the counter, the meter will output 20 pulses.

EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL

9–69

Page 81
Image 81