GROUP 0, FUNCTION 0—THE INTEGRATION INTERVAL

CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP

9.1Group 0, Function 0—The Integration Interval

INTEGRATION INTERVAL: Time which all instantaneous readings are averaged to obtain a max and min demand. The Integration Interval is entered in seconds. When entering 15 minutes, enter: 0900 seconds. The default value is 900 seconds.

To change the Integration Interval:

Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

A B C N

 

 

 

POWER

 

 

 

PF

 

 

 

KW

 

 

 

KVA

KVAH

KWH

FREQ

KVAR

MAX/MIN

POWER PHASE

LIMITS VOLTS AMPS

NEXT

Step 1:

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

A B C N

 

 

 

POWER

 

 

 

PF

 

 

 

KW

 

 

 

KVA

KVAH

KWH

FREQ

KVAR

 

 

MAX/MIN

 

 

 

VOLTS

 

 

 

AMPS

 

 

 

POWER

 

 

 

PHASE

 

 

 

 

 

 

LIMITS

 

 

 

 

 

 

 

 

 

 

 

 

 

NEXT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a. Enter Group Level of Programming Mode (see Chp. 8).

b. Press MAX/MIN/LIMITS until 0. appears in upper display.

c. Press AMPS to activate the Group.

Function 00. appears in upper display. The second 0 indicates Function 0

Lower display indicates current Interval setting.

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 2:

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

a. Press AMPS once to begin Data Entry Sequence.

The previous value shifts to middle display and four dashes appear in lower display.

b. Press VOLTS for desired number.

c. Press AMPS to store.

Group 0, Function 1 — The Meter Address

Repeat this procedure until new Integration Interval is entered.

When complete, middle display blanks and lower display indicates new Integration Interval.

See Chapter 14 to Exit.

9–54

EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL

Page 66
Image 66
GE EPM 5200, EPM 5300, EPM 5350 Group 0, Function 0-The Integration Interval, Enter Group Level of Programming Mode see Chp