GE EPM 5200, EPM 5300 Programming Steps, Enter in Group 0, Function 4, Pack ‘p’, Segments C and D

Models: EPM 5300 EPM 5200 EPM 5350

1 134
Download 134 pages 15.43 Kb
Page 75
Image 75

CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP

6 2 H z

5 8 H z

RELAY MODE

R E S E T

L 2

S E T

L 1

0 H z

Programming Steps:

R E S E T

N O P O W E R T O T H E U N I T R E S E T

ZEnter in GROUP 0, FUNCTION 4, PACK ‘P’, Segment C and D: UP, UP.

ZEnter in GROUP 5, FUNCTION 4, LIMIT 1, Segments B, C, and D: DOWN, UP, DOWN. Value: 58.00.

ZEnter in GROUP 5, FUNCTION 4, LIMIT 2, Segments B, C, and D: UP,

UP, DOWN. Value: 62.00.

EXAMPLE 2: Normally reset—non-event condition is reset relay

Relay 1 will be “SET” if the instantaneous reading for amps is below 4.00 or above 5.00 amps. Under all other conditions the relay will be “RESET”.

Under this setup the relay will NOT act as a protective switch.

Programming Steps:

ZEnter in GROUP 0, FUNCTION 4, PACK ‘p’, Segments C and D:

DOWN, DOWN

ZEnter in GROUP 4, FUNCTION 2, LIMIT 1, Segments: B, C, and D: UP,

UP, DOWN. Value: 5.00

ZEnter in GROUP 4, FUNCTION 2, LIMIT 2, Segments: DOWN, UP,

DOWN. Value: 4.00

Group 0—Function Number

Description

 

 

04.P

Controls Relay 1

 

 

05.P

Controls Relay 2 (and 3 if NL4)

 

 

To change the Relay Mode to either Fail-safe or Reset:

Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL