EPM 5300 Series Meters

Chapter 12: Groups 4, 5 and 6—

Set Limits and

Relays

The EPM 5300P -NL offers a comprehensive limit and set point functionality. The user can program above or below limits for every reading, including %THD. When a voltage or current measurement exceeds a particular value, the set limit is triggered and alerts the user. Each limit can trigger two internal Form C dry contact relays for alarm or secondary protection.

The EPM 5300P offers two set limit points available for each measured function: LM1 and

LM2. Each limit can be set at any desired level. Note: The EPM 5200P does not have limit setting capability.

120

100

80

CURRENT 60 (AMPS) 50 40

20

0

LM1 AND LM2 SET LIMITS

120 LM1 is triggered

LM1 SET TO TRIGGER ABOVE 100 AMPS.

80

 

LM2 SET TO

40 LM2 is triggered

TRIGGER BELOW

50 AMPS.

ABC

PHASES

FIGURE 12–1: Example of LM1/LM2 Set Limits

EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL

12–89

Page 101