CHAPTER 9: PROGRAMMING GROUP 0 - GLOBAL METER SETUP

GROUP 0, FUNCTION 6—KYZ PARAMETER SELECTION

9.8Group 0, Function 6—KYZ Parameter Selection

FUNCTION 6 applies only if Option -NL or -NL2 was ordered.

OPTION -NL: This option gives the meter 2 Relays and one KYZ pulse. The KYZ pulse can be programmed to the below features.

Select a single parameter from Table 9-5according to the EPM 5300P model being programmed.

OPTION -NL2: This option offers 3 distinct KYZ pulses instead of Relays.

Only three separate parameters may be selected: FUNCTION 6.0 (KYZ Port 0), FUNCTION

6.1(KYZ Port 1), and FUNCTION 6.2 (KYZ Port 2). The available parameters vary according to the EPM 5300P model being programmed. For exact port positions see Installation Sections.

 

Table 9–1: KYZ Parameters

 

 

Parameter

Description

 

 

0

Disable KYZ

 

 

1

Positive Watt Hour KYZ

 

 

2

VA Hour KYZ

 

 

3

Negative Watt Hour KYZ

 

 

4

Positive VAR Hour KYZ

 

 

5

Negative VAR Hour KYZ

 

 

APPLICABLE SELECTIONS: 5300P - +WH, -WH, VAH 5300P - +WH, -WH, +VARH, -VARH

To perform the KYZ Parameter Selection:

Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL

9–67

Page 79
Image 79
GE EPM 5300, EPM 5200 Group 0, Function 6-KYZ Parameter Selection, To perform the KYZ Parameter Selection, KYZ Parameters