CHAPTER 10: PROGRAMMING GROUP 1 – VOLTAGE, AMP AND WATT SCALE SETTINGS

GROUP 1, FUNCTION 1

10.2 Group 1, Function 1

- AMPERAGE FULL SCALE -

Table 10–3: Full Scale Settings for Amps

CT Type

Full Scale

 

 

Direct Input

05.00 A

 

 

600/5

0600 A

 

 

1000/5

1000 A

 

 

2000/5

2000 A

 

 

3000/5

03.00 KA

 

 

5000/5

05.00 KA

 

 

Also note that the meter reads with digital accuracy to a 2000 count range. Thus all CT and PT full scale settings in the meter should reflect that limitation. The table above shows the proper settings.