CHAPTER 11: PROGRAMMING GROUP 2 - METER CALIBRATION

GROUP 2, FUNCTIONS 0–2

Step 1:

a. Enter Group Level of Programming Mode (see Chp. 8).

b. Press MAX/MIN/LIMITS until 2. appears in upper display.

c. Press AMPS to activate the Group.

A one digit password is required to continue. d. Press VOLTS until 5 appears.

e.Press AMPS to select.

Step 2:

a. Press MAX/MIN/LIMITS until 22. appears in upper display.

b. Press AMPS to activate. (Calibration begins with Amps A, then moves to B and C).

Middle and lower displays blank.

MAX

AC VOLTS

A B C A B

C

MIN

N N N B C A

LM1

 

 

LM2

AC AMPS

 

 

 

 

A B C N

 

 

POWER

 

 

 

PF

 

 

 

KW

 

 

 

KVA

KVAH

KWH

FREQ

KVAR

MAX/MIN

VOLTS AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 3:

New value moves to middle display.

Lower display indicates the calibrated reading after

10-15 seconds.

To enter the half scale value in lower display, a. Press VOLTS to select digits.

b. Press AMPS to store and proceed to B or C within the group.

c. Press MAX/MIN/LIMITS to end calibration procedure.

See Chapter 14 to Exit.