Friedrich 920-087-04 (3-05) A. Electrical Rating Tables, 15/20A LCDI Device, 30A LCDI Device

Models: 920-087-04 (3-05)

1 28
Download 28 pages 42.35 Kb
Page 13
Image 13
A. Electrical Rating Tables

920-087-04 (3-05)

A. Electrical Rating Tables

All230/208voltunitsareequippedwithpowercords.SeeAppendixBonpage19forwiringinstructionson265Vunits.

NOTE: Use Copper Conductors ONLY. Wire sizes are per NEC, check local codes for overseas applications.

Table 1

250 V Receptacles and Fuse Types

 

AMPS

 

15

20*

 

30

RECEPTACLE

 

 

 

 

 

 

 

 

 

 

TIME-DELAY TYPE FUSE

15

20

 

30

(or HACR circuit breaker)

 

 

 

 

 

HACR – Heating, Air Conditioning, Refrigeration

*May be used for 15 Amp applications if fused for 15 Amp NOTE: 265 volt units are hard wired.

Table 2

Recommended branch circuit wire sizes*

NAMEPLATE / MAXIMUM

AWG WIRE SIZE**

CIRCUIT BREAKER SIZE

 

 

15

14

 

20

12

 

30

10

AWG – American Wire Gauge * Single circuit from main box

** Based on copper wire, single insulated conductor at 60°C

ELECTRIC SHOCK HAZARD! Turn off electric power before service or installation. All electrical connections and wiring MUST be installed by a qualified electrician and conform to the National Electrical Code and all local codes which have jurisdiction. Failure to do so can result in property damage, personal injury and/or death.

WIRE SIZE

Use ONLY wiring size recommended for

single outlet branch circuit.

 

 

 

 

Use ONLY type and size fuse or HACR cir-

FUSE/CIRCUIT

cuit breaker indicated on unit’s rating plate.

Proper current protection to the unit is the

BREAKER

responsibility of the owner. NOTE: A time

 

 

delay fuse is provided with 265V units.

 

 

 

Unit MUST be grounded from branch circuit

 

through service cord to unit, or through sep-

 

arate ground wire provided on permanently

 

connected units. Be sure that branch circuit

GROUNDING

or general purpose outlet is grounded. The

field supplied outlet must match plug on

 

 

service cord and be within reach of service

 

cord. Refer to Table 1 for proper receptacle

 

and fuse type. Do NOT alter the service cord

 

or plug. Do NOT use an extension cord.

 

 

 

The field supplied outlet must match plug on

RECEPTACLE

service cord and be within reach of service

cord. Refer to Table 1 for proper receptacle

 

and fuse type. Do NOT alter the service cord

 

or plug. Do NOT use an extension cord.

 

 

 

Use recommended wire size given in Table

WIRE SIZING

2 and install a single branch circuit. All wiring

must comply with local and national codes.

 

 

NOTE: Use copper conductors only.

 

 

B. Power Cord Information (230/208V models only)

All Friedrich 230/208V PTAC units are shipped from the factory with a Leakage Current Detection Interrupter (LCDI) equipped power cord. The LCDI device meets the UL and NEC requirements for cord connected air conditioners effective August 2004.

To test your power supply cord:

1.Plug power supply cord into a grounded 3 prong outlet.

2.Press RESET.

3.Press TEST (listen for click; Reset button trips and pops out).

4.Press and release RESET (listen for click; Reset button latches and remains in). The power supply cord is ready for operation.

Figure10a

 

4.1"

 

 

 

15/20A LCDI Device

2"

RESET

TEST

 

 

Test Button

 

 

Reset Button

NOTE: The LCDI device is not intended to be used as a switch.

Once plugged in the unit will operate normally without the need to reset the LCDI device. If the LCDI device trips and requires resetting the cause of the trip should be identified prior to further use of the PTAC.

If the device fails to trip when tested or if the power supply cord is damaged it must be replaced with a new supply cord obtained from the product manufacturer, and must not be repaired.

Figure10b

30A LCDI Device

7"

2"

Test Button

Reset Button

13

Page 13
Image 13
Friedrich 920-087-04 (3-05) A. Electrical Rating Tables, B. Power Cord Information 230/208V models only, 30A LCDI Device