Protector is

activated due to

overheating of the compressor

Refrigerant is insuffi cient or super abundance

Capillary is blocked and the suction

temperature is rising

The compressor can run smoothly or is stuck.

The air discharge valve is damaged.

Adjust the quantity of the refrigerant

Replace capillary

Replace the compressor

Compressor

is ON-OFF frequently

 

 

 

 

Use the multimeter to check whether the contact point of the

 

Protector has malfunction

 

 

 

compressor is conducted at the timer of non-subheating. If it

 

 

 

 

 

 

 

can’t be conducted, please replace the protector.

 

 

 

 

 

 

 

 

 

 

 

 

 

Supply voltage is abnormal

 

 

Check the reason, improve the power supply condition and

 

 

 

add the regulated power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The radiating for evaporator and condensor is

 

 

Get rid of the dust on the evaporator and condensor, remove

 

not good; Poor air ventilation

 

 

the obstacles at the air outlet

 

 

 

 

 

 

 

 

 

The air conditioner capability does not match

 

 

 

 

the area of the room, i.e. so called “Big system,

 

 

Slect the A/C which is applicable to the room areas

 

 

 

 

 

 

 

small room”.

 

 

 

 

 

 

 

 

 

 

 

 

Reveiving distance of remote control

is too short

LCD display fl ashes or when pressing the transmit button the entire screen is displayed.

Replace the battery

Battery’s capacity is insuffi cient

Replace the battery

Replace the battery

LED display is found short of stroke

The LCD frame hasn’t fi xed well

Fix the LCD frame properly

Vibration and noise are abnormal

The compressor hasn’t installed well and the

base is unstable

The unit hasn’t placed fl atly and stable

The unit’s support is unstable

Check whether the base is fi rm

Adjust the unit’s position

Strengthen the support or refi t it

There are foreign objects on the unit

Get rid of the foreign objects

Screws are loosened

Tighten the screws