Frymaster MH14, BIH14 2.2After Fryers Are Under The Fry Station Hood, 2.3Power Requirements

Models: MH14 BIH14

1 27
Download 27 pages 49.91 Kb
Page 9
Image 9
2.2After Fryers Are Under The Fry Station Hood

2.2After Fryers Are Under The Fry Station Hood

Adjust casters so that fryers are level and at the proper height in the fry station hood. If necessary, level the fryer(s) by loosening the locking screw on the caster leg and screwing the caster in or out. When fryer is level and at proper height, retighten the locking screw on the caster leg.

Secure the fryer in place under the hood with the restraining hardware installed with the hood.

2.3Power Requirements

2.3Power Requirements DANGER

Copper wire suitable for at least 167°F (75°C) MUST be used for power connections.

 

 

 

WIRE

MIN.

AWG

AMPS PER LEG

MODEL

VOLTAGE

PHASE

SERVICE

SIZE

(mm2)

L1

L2

L3

H14

208

3

3

6

(16)

39

39

39

H14

240

3

3

6

(16)

34

34

34

H14

480

3

3

8

(10)

17

17

17

H14

220/380

3

4

6

(16)

21

21

21

H14

240/415

3

4

6

(16)

20

20

21

H14

230/400

3

4

6

(16)

21

21

21

ALL

208

3

3

6

(16)

39

39

39

14 SERIES

240

3

3

6

(16)

34

34

34

EPRI

220/380

3

4

6

(16)

21

21

21

UNITS

240/415

3

4

6

(16)

20

20

20

Manual background DANGER

The electrical power supply for this appliance MUST be the same as indicated on

the rating and serial number plate located on the inside of the fryer door.

Manual background DANGER

This appliance MUST be connected to the voltage and phase as specified on the

rating and serial-number plate located on the inside of the fryer door.

Manual background DANGER

All wiring connections for this appliance MUST be made in accordance with the wiring diagrams furnished with the equipment. Wiring diagrams are located on the inside of the fryer door.

2–2

Page 9
Image 9
Frymaster MH14, BIH14 warranty 2.2After Fryers Are Under The Fry Station Hood, 2.3Power Requirements