2.4Pre-Connection Preparations (cont.)
4.For rethermalizers equipped with casters, there are no
WARNING
Inlet water pressure must not exceed 80 PSI. A regulator must be installed between
rethermalizer water inlet and water supply when pressure exceeds 80 PSI.
5.Connect the water hose to the fitting at the rear of the unit. If inlet water pressure exceeds 80 PSI, a regulator must be installed to prevent damage to rethermalizer. Ensure that water pressure to rethermalizer is less than 80 PSI.
NOTE 1: The unit may be equipped with an optional hose assembly with a
4.Connect the desired drain plumbing to the 1¼" drain valve.
5.Test the equipment’s electrical system by plugging the power cord into a grounded 120VAC
outlet and pressing the computer’s ON/OFF button.
6.Turn the computer off. Verify that the display is blank.
7.Verify that the minimum and maximum incoming gas pressures for the type of gas to be used are in accordance with the accompanying table.
Incoming Gas Pressures
Gas | Minimum | Maximum |
| 6" W.C. | 14" W.C. |
Natural | 1.49 kPa | 3.48 kPa |
| 14.93 mbar | 34.84 mbar |
| 11" W.C. | 14" W.C. |
LP | 2.74 kPa | 3.48 kPa |
| 27.37 mbar | 34.84 mbar |
2.4.1 Connecting to the Gas Supply
GAS CONNECTIONS AND PIPE SIZES
The size of the gas supply pipe is very important. If the pipe is too small, the gas pressure at the burner manifold will be low. This will cause slow recovery and delayed ignition. The incoming gas supply line should be a minimum of 1½ inches (38mm) ID.