Relay/Transformer (R/T Box)

Standard Transition

Each MX250 microprocessor based ATS controller requires a relay/transformer box to apply line voltage to the ATS operator via coil control relays. Also required is power for the MX150 printed circuit board and an appli- cation of sensing voltage proportional to line voltage. This is accomplished by the relay transformer box. This method of switching operator voltage and applying power and sensing voltage to the printed circuit board isolates

1

2

(inside)

3

Figure 12

40-225 Amp Molded Power Section

Transformer Usage (see Figure 12)

R/T Box

Primary

1 VA

25 VA

Assembly

Voltage

XFMR

XFMR

Part No.

at 50/60 Hz

Part No.

Part No.

 

 

 

 

57P-1015

120V

K-3216

K-3224

57P-1016

208-220V

K-3217

K-3225

57P-1017

230-240V

K-3218

K-3226

57P-1018

277V

K-3219

K-3227

57P-1019

380-400V

K-3220

K-3228

57P-1020

416-440V

K-3221

K-3229

57P-1021

460-480V

K-3222

K-3230

57P-1022

575-600V

K-3223

K-3231

 

 

 

 

Bill of Material

Item

Part No.

Description

Qty

 

 

 

 

1

See Chart

Transformer (1 VA)

2

2

See Chart

Transformer (25 VA)

2

3

K-1274

Relay Flange Mounted

2

 

 

 

 

the MX250 from the line voltage, further protecting

the controller from harmful line transients. Two versions of the R/T box exist depending on the type of ATS (standard transition or delayed transition).

The following layout drawings of the R/T Box compo- nents (standard and delayed transition) include a bill of materials for replacement parts. Schematics are included to indicate proper wiring.

PRI.

PRI.

PRI.

 

SEC.

 

1

SEC.

SEC.

 

2

3

Figure 13

40-3000 Amp - All Other Standard Types

Transformer Usage (see Figure 13)

R/T Box

Primary

1 VA

25 VA

Assembly

Voltage

XFMR

XFMR

Part No.

at 50/60 Hz

Part No.

Part No.

 

 

 

 

50P-1026

120V

K-3216

K-3224

50P-1027

208-220V

K-3217

K-3225

50P-1028

230-240V

K-3218

K-3226

50P-1029

277V

K-3219

K-3227

50P-1030

380-400V

K-3220

K-3228

50P-1031

416-440V

K-3221

K-3229

50P-1032

460-480V

K-3222

K-3230

50P-1033

575-600V

K-3223

K-3231

 

 

 

 

Bill of Material

Item

Part No.

Description

Qty

 

 

 

 

1

See Chart

Transformer (25 VA)

2

2

See Chart

Transformer (1 VA)

2

3

K-1260

Coil Control Relay (24V)

2

 

 

 

 

26

Entelli-Switch 250 Operation and Maintenance Manual (71R-2000)

GE Zenith Controls

Page 26
Image 26
GE Entelli-Switch 250 manual Relay/Transformer R/T Box, Amp Molded Power Section Transformer Usage see Figure