Safety / Installation

DANGER

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.

The safe operation of your switch is GE Zenith’s focus. The proper storage, installation, operation and mainte- nance will help increase the life of the switch.

CAUTION

Due to hazardous voltage and current, GE Zenith rec- ommends that a GE Zenith Certified technician or a qualified electrician must perform the

installation and maintenance of the switch.

Equipment Inspection and Storage

Once you have received the transfer switch, inspect it for any damage. This includes damage to the enclosure, power panel, control panel and wiring harness. If any damage is found or suspected, file a claim as soon as possible with the carrier and notify the nearest GE Zenith representative.

Before installation, if it is necessary, store the transfer switch in a clean dry place, protected from dirt and water. Provide ample air circulation and heat, if neces- sary, to prevent condensation.

 

Operating

 

Storage

Temperature

 

Temperature

(Ambient):

Humidity

 

 

 

Final Equipment Inspection

Prior to energizing the transfer switch:

1.Remove any debris incurred, with a vacuum, due to shipment or installation.

2.Verify that all cabled connections are

correct and that phase rotation of both sources match.

3.Check engine start connections.

4.Verify the correct connection of all control wires.

5.Check settings of all timers and adjust as necessary.

6.Adjust any optional accessories as required.

7.Check the lug torque values of the power connections.

NOTE: Lug torque values are specified in the power panel manual.

8.Make sure that all covers and barriers are installed and properly fastened.

NOTE: Power panels ship from GE Zenith in Source 1 Position.

WARNING

Do not use a blower since debris may become lodged in the electrical and mechanical components and cause damage.

-30°C to

40-400 AMP

5% to 95%

+75°C

(molded shell)

(non-con-

(-22°F to

-20°C to +65°C

densing)

+167°F)

(-4°F to +149°F)

 

 

40-4000 AMP

 

 

(all other frame

 

 

and panel types)

 

 

-20°C to +60°C

 

 

(-4°F to +140°F)

 

 

 

 

Table 1

Each GE Zenith transfer switch is factory wired and tested. A complete information package is furnished with each switch which includes:

a.Sequence of operation.

b.Description and operation of all accessories supplied.

c.Power panel connection diagram and schematic.

d.Description and identification of all customer field connections.

Installation of GE Zenith transfer switches includes:

a.Mounting the transfer switch cabinet.

b.Connection of Source 1, Source 2, and Load cables or bus bars.

c.Connection of external control circuits as required.