Section 9 — Installation Drawings

Guardian Liquid-cooled 40 kW Generators Installation Drawing – Drawing No. 0D5335

RECOMMENDED FUEL/ELECTRICAL STUB-UPS (SEE TOP VIEW)

DESCRIPTION

 

INSIDE

 

BASE

 

 

AC LOAD LEAD CONDUIT

(LEFT)

 

A1

INSIDE STUB-UP FOR

 

 

 

 

 

 

C

 

FUEL CONNECTIONS

 

 

 

 

 

 

 

 

 

 

 

NOTE:

FUEL SYSTEM SET UP WITH OUTSIDE STUB UPS (SEE LEFT SIDE VIEW). SMALL FUEL SYSTEM MODIFICATIONS REQUIRED FOR

INSIDE STUB-UPS.

WEIGHT DATA

UNIT: 729.7 kg [1609 lbs]

STEEL COMPARTMENT: 208.6 kg [460 lbs]

UNITS: mm [INCHES]

965 [37.99"]

1160 [45.67"]

877 [34.51"]

REAR VIEW

NOTES:

1.STANDARD BLOCK HEATER REQUIRES 120V AC CONNECTION

2.CONNECTION POINTS FOR AC LOAD LEADS, TRANSFER SWITCH, AND

ENGINE AUTOMATIC START/STOP CONTROL WIRES PROVIDED IN

AC CONNECTION PANEL.

3.EXHAUST MUFFLER SUPPORT BRACKETS SUPPLIED WITH OPTIONAL COMPARTMENT.

4.12 VOLT NEGATIVE GROUND SYSTEM

BATTERY TRAY INSIDE DIMENSIONS: 178 X 342.5 [7" X 13.5"]

5.2.5" I.D. FLEX EXHAUST

6.MAIN LINE CIRCUIT BREAKER.

7.DOORS MUST BE OPENED 90 DEG. TO BE REMOVED.

8. A1 MAY BE USED

FOR CIRCUIT BREAKER STUB-UP LOCATION.

9.SEE DRAWING C3850 FOR DUCT REMOVAL. REMOVAL OF FRONT DUCT WILL PROVIDE ACCESS TO MUFFLER FOR SERVICING.

ENGINE SERVICE CONNECTIONS

INLET NATURAL GAS = 3/4" NPT COUPLING

OIL DRAIN = 1/2" NPT COUPLING

EXHAUST OUTLET -

2.5" OD MUFFLER OUTLET

(1) 12V BATTERY SEE NOTE 4

LIFTING EYE

(4 PLACES)

158 [6.22"]

CENTER OF

GRAVITY

981 [38.62"]

1930 [75.98"]

RIGHT SIDE VIEW

Generac® Power Systems, Inc. 57

Page 59
Image 59
Generac 004626-1, 004373-2, 004373-2, 004626-1 owner manual 12V Battery see Note Lifting EYE Places