Section 1 - General Information
Guardian
GENERATOR
This equipment is an
These models are available. They are rated as follows:
AUTOMATIC SYSTEM OPERATION
When this generator along with its transfer switch has been installed and interconnected, a circuit board in the generator panel constantly monitors utility power source voltage. Should that voltage drop below a preset value, and remain at such a low state for a preset amount of time, the generator cranks and starts. After the generator starts, the transfer switch transfers load circuits so the generator can power them.
When utility source voltage has been restored, the switch
Model 004090: Provides 10,000 watts (10 kW) of
Model 004091: Provides 10,000 watts (10 kW) of
Model 004124: Provides 10,000 watts (10 kW) of
Model 004125: Provides 10,000 watts (10 kW) of
Model 004092: Provides 15,000 watts (15 kW) of 1 phase power.
Model 004093: Provides 15,000 watts (15 kW) of 3 phase power.
Model 004126: Provides 15,000 watts (15 kW) of 1 phase power.
Model 004127: Provides 15,000 watts (15 kW) of 3 phase power.
Model 004094: Provides 20,000 watts (20 kW) of
Model 004095: Provides 20,000 watts (20 kW) of
Model 004128: Provides 20,000 watts (20 kW) of
Model 004096: Provides 25,000 watts (25 kW) of 1 phase power.
Model 004097: Provides 25,000 watts (25 kW) of 3 phase power.
Model 004130: Provides 25,000 watts (25 kW) of 1 phase power.
Model 004131: Provides 25,000 watts (25 kW) of 3 phase power.
Model 004474: Provides 25,000 watts (25 kW) of 1 phase power.
Model 004475: Provides 25,000 watts (25 kW) of 1 phase power.
WARNING: If this generator is used to power electrical load circuits normally powered by a utility power source, you are required by code to install a transfer switch. The transfer switch must effectively isolate the electric system from the utility distribution system when the generator is operating (NEC 701). Failure to isolate an electri- cal system by such means results in damage to the generator and may also result in injury or even death to utility power workers due to back- feed of electrical energy.
GENERATOR AC
CONNECTION SYSTEMS
The generator was shipped from the factory with its sta- tor AC output leads connected in one of the “Delta” con- figurations, as shown in Figure 2. This type of connec- tion system will supply a 120 and/or 240 volts, 1 or
Figure 2 - Generator AC Connection System
If, however, load voltage requires 120/208 volts,
4 Generac® Power Systems, Inc.