Standby Generator Sets

Installation

START-UP CHECKLIST

Before working on the generator, ensure the fol- lowing:

The AUTO/OFF/MANUAL switch is in the OFF position.

The 120VAC supply to the battery charger is switched OFF.

‹PREPARATION FOR START-UP

Ensure that the 120VAC circuit breaker to the bat- tery charger is open.

Remove the fuse from the the control panel. For the H-100 and R-100: Open the front door of the control box and remove the 15 Amp ATO fuse in the lower left-hand corner of the control box.

Connect the battery cables to the battery. Attach negative battery cable last.

Close the 120VAC circuit breaker to the battery charger.

Measure the voltage at the battery before and after the charger is turned on.

Verify all AC electrical connections are tight at the circuit breaker and transfer switch.

Visually inspect entire area looking for loose paper, plastic wrappings, leaves, etc.

Check all hoses clamps fittings for leaks or dam- age.

Check all electrical plugs throughout the genera- tor. Ensure each plug is seated correctly and fully inserted into its receptacle.

Verify the AUTO/OFF/MANUAL switch is in OFF position.

Open the valve to the engine fuel line.

Bleed the fuel system of air. (necessary for long fuel lines).

Open the generator main line circuit breaker.

Connect a manometer to the gas line and record the static pressure. It must be as listed in the Specifications.

Insert the fuse into the control panel.

Move the AUTO/OFF/MANUAL switch to the MAN- UAL position. The engine should now crank and start.

Check voltage at the generator terminals.

For 3-phase units, check phase rotation at the transfer switch terminals. The generator phase rotation must match the utility phase rotation.

Check for coolant, fuel, oil, and exhaust leaks.

Close the generators main line circuit breaker.

Turn the generator set off.

Connect the UTILITY supply to the transfer switch.

Set the AUTO/OFF/MANUAL switch to AUTO.

Disconnect utility power before the transfer switch.

Engine should start, transfer to load.

Run at least 15 minutes on generator power. Make certain all 3-phase loads are functioning correctly (correct phase rotation).

Reconnect Utility power

Transfer switch will transfer back to Utility and engine will shut down within the given time parameters set up for the specific transfer switch and controller.

Install all covers, access plates and door panels.

Put the Owners Manual in a safe and accessible place.

Make certain the AUTO/OFF/MANUAL switch is in the AUTO position.

‹START-UP INSPECTION

When a start-up is performed by an Authorized Service Dealer, a standard three-part form titled “Start-up Inspection for Standby Power Systems” (part no. 067377), should be completed by the instal- lation technician or engineer. See page 1-3 for infor- mation on locating the nearest Authorized Service Dealer. The installer should complete the form and disseminate copies as follows:

White copy: Mail to Generac Warranty Department, P.O. Box 340, 211 Murphy Dr., Eagle, WI 53119- 2062.

Pink Copy: For service file of installing dealer.

Yellow Copy: For the customer’s records.

11/05 A .Rev Install001

8-2

Page 14
Image 14
Generac Power Systems 005219-0 owner manual START-UP Checklist, ‹ Preparation for START-UP, ‹ START-UP Inspection

005219-0 specifications

Generac Power Systems 005219-0 is a robust and versatile backup power generator designed for residential and commercial applications. Known for its reliability and advanced features, this generator ensures that you have a dependable power source when you need it the most, particularly during unexpected outages.

One of the standout features of the Generac 005219-0 is its powerful engine. It is equipped with a 22 kW capacity, which is sufficient to power essential appliances and systems in your home or business. This power allows for the simultaneous operation of multiple devices, such as refrigerators, air conditioning units, and electronics, without the worry of overloading the system.

Generac’s patented Quiet-Test Technology is another significant characteristic of the 005219-0, which enables the generator to run at a lower RPM during weekly self-tests. This feature not only ensures that the generator is in optimal condition but also minimizes noise, making it less intrusive for homeowners while providing peace of mind that the generator is ready when needed.

The generator utilizes an automatic transfer switch, which instantly switches your home's power source from the grid to the generator in the event of a power failure. This seamless transition prevents any disruption in your daily activities and protects sensitive electronics from power surges.

Additionally, Generac is known for its tough design and weather-resistant features. The generator is constructed with durable materials to withstand various weather conditions, making it suitable for outdoor placement. Furthermore, the unit typically comes with a corrosion-resistant aluminum enclosure, ensuring longevity and reduced maintenance.

The 005219-0 also includes user-friendly control options, which are facilitated by a digital controller that provides easy monitoring and management of the generator’s functions. This capability allows users to track power consumption, manage maintenance schedules, and diagnose any potential issues quickly.

Lastly, Generac stands behind its products with comprehensive warranties, providing customers with assurance and confidence in their investment. With excellent customer service and support, owning a Generac generator like the 005219-0 means you are investing in a reliable power solution that meets your energy needs effectively.