Standby Generator Sets

Maintenance

MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES

Before working on the generator, ensure the fol- lowing:

The AUTO/OFF/MANUAL switch is in the OFF position.

The 15A fuse has been removed from the con- trol box.

The 120VAC supply to the battery charger is switched OFF.

‹EVERY THREE MONTHS

1.Check battery state of charge and condition.

2.Inspect and test fuel system.

3.Check transfer switch.

4.Inspect exhaust system.

5.Check engine ignition system.

6.Check fan belts.

‹ONCE EVERY SIX MONTHS

1.Test Engine Safety Devices (low oil pressure, low coolant level, high coolant temperature).

‹ONCE ANNUALLY

1.Test engine governor. Adjust or repair, if needed.

2.Clean, inspect generator.

3.Flush cooling system.

‹FIRST 100 OPERATING HOURS

1.Change engine oil and oil filter. (After initial change, service engine oil and filter at 150 operat- ing hours or 6 months, whichever comes first.)

‹EVERY 500 OPERATING HOURS

1.Service air cleaner.

2.Check starter.

3.Check engine DC alternator.

COOLING SYSTEM

Air intake and outlet openings in the generator com- partment must be open and unobstructed for contin- ued proper operation. This includes such obstruc- tions as high grass, weeds, brush, leaves and snow.

Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down.

The exhaust system parts from this product get extremely hot and remain hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.

CHECKING FLUID LEVELS

‹CHECK ENGINE OIL

Check engine crankcase oil level (Figure 10.1) at least every 20 hours of operation, or prior to use.

Remove oil dipstick and wipe dry with a clean, lint- free cloth.

Install oil dipstick, then remove again.

Oil should be between FULL and ADD marks.

If oil level is below the dipstick ADD mark, remove oil fill cap. Add the recommended oil to bring oil level up to the FULL mark. DO NOT FILL ABOVE THE “FULL” MARK. See “Engine Oil Recommendations” for recommended oils.

Figure 10.1 - Oil Dipstick and Oil Fill Cap

Oil Dipstick

Oil Fill

 

Oil Filter

‹BATTERY FLUID

Check battery electrolyte fluid at least once weekly. Fluid should cover separators in all battery cells. If fluid level is low, add distilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.

10-1

08/05

0 .Rev Maint001

Page 16
Image 16
Generac Power Systems 005219-0 owner manual Cooling System, Checking Fluid Levels

005219-0 specifications

Generac Power Systems 005219-0 is a robust and versatile backup power generator designed for residential and commercial applications. Known for its reliability and advanced features, this generator ensures that you have a dependable power source when you need it the most, particularly during unexpected outages.

One of the standout features of the Generac 005219-0 is its powerful engine. It is equipped with a 22 kW capacity, which is sufficient to power essential appliances and systems in your home or business. This power allows for the simultaneous operation of multiple devices, such as refrigerators, air conditioning units, and electronics, without the worry of overloading the system.

Generac’s patented Quiet-Test Technology is another significant characteristic of the 005219-0, which enables the generator to run at a lower RPM during weekly self-tests. This feature not only ensures that the generator is in optimal condition but also minimizes noise, making it less intrusive for homeowners while providing peace of mind that the generator is ready when needed.

The generator utilizes an automatic transfer switch, which instantly switches your home's power source from the grid to the generator in the event of a power failure. This seamless transition prevents any disruption in your daily activities and protects sensitive electronics from power surges.

Additionally, Generac is known for its tough design and weather-resistant features. The generator is constructed with durable materials to withstand various weather conditions, making it suitable for outdoor placement. Furthermore, the unit typically comes with a corrosion-resistant aluminum enclosure, ensuring longevity and reduced maintenance.

The 005219-0 also includes user-friendly control options, which are facilitated by a digital controller that provides easy monitoring and management of the generator’s functions. This capability allows users to track power consumption, manage maintenance schedules, and diagnose any potential issues quickly.

Lastly, Generac stands behind its products with comprehensive warranties, providing customers with assurance and confidence in their investment. With excellent customer service and support, owning a Generac generator like the 005219-0 means you are investing in a reliable power solution that meets your energy needs effectively.