Standby Generator Sets

Operation

GENERATOR CONTROL AND

OPERATION

Refer to the appropriate control panel operator’s manual for this unit.

OPERATING UNIT WITH MANUAL TRANSFER SWITCH

If the generator was installed in conjunction with a transfer switch capable of manual operation only, the following procedure applies. A manually operated transfer switch is one that will not provide automatic start-up and does not include an intelligence circuit.

‹ENGINE START-UP AND TRANSFER

For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.

DANGER

The Maintenance Disconnect Switch and the AUTO/OFF/MANUAL switches (if so equipped) must be set properly, or the generator will crank and start as soon as the utility power to the transfer switch is turned off. Refer to applicable control panel and transfer switch manuals for more information.

Do not proceed until certain that utility source voltage is available to the transfer switch and the transfer switch main contacts are set to

UTILITY.

Do not attempt manual operation until all power supplies to the transfer switch have been posi- tively turned off, or extremely dangerous - pos- sibly lethal - electrical shock will result.

Transfer switch enclosure doors should be kept closed and locked. Only authorized personnel should be allowed access to the transfer switch interior. Extremely high and dangerous voltages are present in the transfer switch.

In order to transfer load from the utility source to the generator, follow these directions:

Turn OFF or disconnect the utility power circuit to the transfer switch, using the means provided (such as the utility source main line circuit break- er).

Set the transfer handle to its UTILITY (NORMAL) position with load circuits connected to the utility power supply.

Set the standby generator’s main line circuit break- er to its OFF (or OPEN) position.

Start the generator.

Do not crank the engine continuously for longer than 30 seconds, or the heat may

damage the starter motor.

Let engine stabilize and warm up.

Check all applicable instrument and gauge read- ings. When certain that all readings are correct, move the transfer switch manual handle to its STANDBY (GENERATOR) position, i.e., load cir- cuits supplied by the generator.

Set the standby generator’s main line circuit break- er to its ON (or CLOSED) position.

Load circuits are now powered by the standby generator.

‹RETRANSFER AND SHUTDOWN

For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.

To transfer the load back to the utility power source and shut down the generator, follow these direc- tions:

Set the standby generator’s main line circuit break- er to its OFF (or OPEN) position.

Manually move the transfer switch handle to its UTILITY (NORMAL) position, i.e., load circuits connected to the utility.

Turn ON the utility power supply to the transfer switch, using the means provided (such as the util- ity power source main line circuit breaker).

Let the generator run at no-load for a few minutes to stabilize internal temperatures.

Shut down the generator.

OPERATING UNIT WITH AUTOMATIC TRANSFER SWITCH

If the generator has been installed with an automatic transfer switch, such as an RTS, HTS, or GTS-type transfer switch, the engine may be started and stopped automatically or manually.

NOTE:

Refer to the applicable manual for your trans- fer switch and to “Transfer Switch Start Signal Connections”. In addition, please note the dangers under “Engine Start-up and Transfer.”

9-1

08/05

0 .Rev Oper001

Page 15
Image 15
Generac Power Systems 005219-0 owner manual Generator Control Operation, Operating Unit with Manual Transfer Switch

005219-0 specifications

Generac Power Systems 005219-0 is a robust and versatile backup power generator designed for residential and commercial applications. Known for its reliability and advanced features, this generator ensures that you have a dependable power source when you need it the most, particularly during unexpected outages.

One of the standout features of the Generac 005219-0 is its powerful engine. It is equipped with a 22 kW capacity, which is sufficient to power essential appliances and systems in your home or business. This power allows for the simultaneous operation of multiple devices, such as refrigerators, air conditioning units, and electronics, without the worry of overloading the system.

Generac’s patented Quiet-Test Technology is another significant characteristic of the 005219-0, which enables the generator to run at a lower RPM during weekly self-tests. This feature not only ensures that the generator is in optimal condition but also minimizes noise, making it less intrusive for homeowners while providing peace of mind that the generator is ready when needed.

The generator utilizes an automatic transfer switch, which instantly switches your home's power source from the grid to the generator in the event of a power failure. This seamless transition prevents any disruption in your daily activities and protects sensitive electronics from power surges.

Additionally, Generac is known for its tough design and weather-resistant features. The generator is constructed with durable materials to withstand various weather conditions, making it suitable for outdoor placement. Furthermore, the unit typically comes with a corrosion-resistant aluminum enclosure, ensuring longevity and reduced maintenance.

The 005219-0 also includes user-friendly control options, which are facilitated by a digital controller that provides easy monitoring and management of the generator’s functions. This capability allows users to track power consumption, manage maintenance schedules, and diagnose any potential issues quickly.

Lastly, Generac stands behind its products with comprehensive warranties, providing customers with assurance and confidence in their investment. With excellent customer service and support, owning a Generac generator like the 005219-0 means you are investing in a reliable power solution that meets your energy needs effectively.