Section 3 — Post Installation Start-up and Adjustments

Air-cooled 15 kW Generators

3.5CHECKING AUTOMATIC

OPERATION

To check the system for proper automatic operation, proceed as follows:

1.Set the generator’s main circuit breaker to it’s OFF (or open) position.

2.Check that the AUTO/OFF/MANUAL switch is set to OFF.

3.Manually set the transfer switch to the UTILITY position, i.e., load terminals connected to the util- ity power source side.

4.Turn ON the utility power supply to the transfer switch, using the means provided (such as a util- ity main line circuit breaker).

5.Set the AUTO/OFF/MANUAL switch to AUTO. Then set the generator’s main circuit breaker to its ON (or closed) position. The system is now ready for automatic operation.

6.Turn OFF the utility power supply to the transfer switch.

With the AUTO/OFF/MANUAL switch at AUTO, the engine should crank and start when the utility source power is turned OFF. After starting, the transfer switch should connect load circuits to the standby side. Let the system go through its entire automatic sequence of operation.

With the generator running and loads powered by generator AC output, turn ON the utility power supply to the transfer switch. The following should occur:

After about 15 seconds, the switch should transfer loads back to the utility power source.

About one minute after retransfer, the engine should shut down.

3.6ADJUSTING THE REGULATOR

(NATURAL GAS ONLY)

Although the generator has been factory set to pro- vide maximum power, it may be necessary in some areas to adjust this setting. Because natural gas has different BTU or power content across the country the engine may not perform as designed.

If experiencing engine problems at high or full load conditions follow these steps. It will require a fre- quency meter to perform this procedure.

1.Turn off utility power to the main distribution panel in the house. This can be done by switching the service main breaker to the off or open posi- tion.

2.Allow the generator to start before loading the generator. Confirm the no-load frequency with the roof open and door off is set at 63-63.5 Hz. Transfer load to emergency circuits.

3. Turn on electrical loads. Be cautious not to over- load the generator. Use the following chart as a guide:

 

Model

120 Volts

240 Volts

 

 

005176

108.3 amps

54.1 amps

 

 

 

 

 

 

4. When full load has been achieved. Connect a fre- quency meter to the output lugs of the generator’s main line circuit breaker.

5. The fuel regulator is fitted with two adjustment screws. While watching the frequency meter, slowly turn the adjustment screw clockwise or counterclockwise one at a time until highest fre- quency is read on the meter. Only limited adjust- ment is available between the set pins. Under no circumstances should any of the pins be removed (Figures 3.1 and 3.2).

Figure 3.1 — Dual Fuel Regulators

V-twin Engine

410cc E

Adjustment

Adjustment

Screw

Screw

(One Side

(Both Sides)

Only)

 

Set Pin

(Both Sides)

6.When the highest frequency is reached maximum power has been set. Then turn both adjustment screws 1/4 turn counterclockwise. Regulator is now set.

Figure 3.2 — Placement of Regulator

Adjustment Screw

12

Page 14
Image 14
Generac Power Systems 05176-0 owner manual Checking Automatic Operation, Adjusting the Regulator Natural GAS only

05176-0 specifications

Generac Power Systems 05176-0 is a powerful home standby generator designed to provide reliable backup power during outages. Known for its innovative technology and robust features, the 05176-0 model is part of Generac's Guardian Series, which is renowned for its reliability and ease of use.

One of the standout features of the Generac 05176-0 is its Generac G-Force engine, which is designed specifically for generator use. This automotive-grade engine is built to handle the rigors of prolonged operation, ensuring that homeowners have a dependable source of power. With a power output of 22 kW, it can handle the essential electrical loads of many homes, allowing users to power their lights, appliances, HVAC systems, and other necessary devices without interruption.

The 05176-0 comes equipped with a state-of-the-art transfer switch that automatically detects outages and begins the power restoration process within seconds. This automatic transfer switch eliminates the need for manual intervention, giving homeowners peace of mind that their power supply will seamlessly transition during a grid failure.

In terms of fuel efficiency, the Generac 05176-0 operates on either natural gas or liquid propane, providing flexibility for installation and operation. Its dual-fuel capability allows users to choose the fuel source that is most convenient and cost-effective for them.

Another notable feature is the generator’s Quiet-Test technology, which runs the generator at reduced RPMs for a self-test every week. This helps to ensure that the generator is operational and ready when needed while minimizing noise pollution in residential areas.

The model also boasts an intuitive LCD display that provides real-time information on the generator's status, including maintenance intervals and diagnostic information. This user-friendly interface simplifies monitoring and helps ensure that users can maintain optimal performance.

Moreover, the construction and design of the 05176-0 are intended for durability and weather resistance. With a robust enclosure made from high-quality materials, it is built to withstand harsh weather conditions, allowing homeowners to trust that their generator will perform reliably in any situation.

Overall, the Generac Power Systems 05176-0 stands out as a premium choice for homeowners seeking a reliable, efficient, and easy-to-use standby generator. Its combination of power output, advanced technology, and user-friendly features makes it an essential investment for anyone looking to ensure that they remain powered during outages.