4 Flue

NOTE:

The flue must be installed in accordance with the current issue of BS5440 Part 1.

Important. The flue must be installed with a fall of 35mm per metre (2o) towards the boiler, see diagram 4.1.

It is of no advantage to exceed this angle (2o) indeed sealing of the fan to flue elbow may become more difficult as the angle is increased.

The air and flue duct connect to the top of the boiler using an elbow which can be positioned to the side or rear.

The rear and side flue assemblies are designed for internal installation, but if necessary, due to insufficient clearances (boiler/flue terminal location) they can be installed from the outside.

For a wall thickness up to 300mm the flue can be fully installed from the inside.

For a wall thickness over 300mm the external cut hole will need to be made good from the outside.

The standard flue is able to provide the duct lengths as shown in diagram 4.2 for a rear flue and diagram 4.3 for a side flue.

If a longer flue duct is required, do not extend the ductings. A 1, 2 or 3metre long flue system and terminal can be supplied.

 

 

6860

 

'R'

 

REAR FLUE LENGTHS

 

 

R = Wall Thickness

 

STD Flue pack

75mm to 442mm

 

1m Flue pack

75mm to 953mm

 

2m Flue pack

75mm to 1953mm

 

3m Flue pack

75mm to 2933mm

 

 

Diagram 4.2

 

'S'

6861

 

 

Make sure flue slopes

 

 

 

 

 

2˚ down towards

 

 

 

 

 

 

 

 

 

 

the boiler

 

 

300mm

 

that is 35mm fall

 

 

 

 

 

 

 

 

 

 

 

per metre

 

 

 

 

 

 

of flue

 

 

 

 

 

 

 

 

 

 

 

 

 

length (2˚)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2˚

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REAR FLUE

SIDE VIEW

35mm

Make sure flue slopes 2˚ down

towards the boiler

that is 35mm fall per metre of flue length (2˚)

2˚

1metre

SIDE FLUE

FRONT VIEW

0158M

10.5mm

Diagram 4.1

SIDE FLUE LENGTHS

S = "External wall face" to "boiler casing"

STD Flue pack

80mm to 331mm

 

 

1m Flue pack

80mm to 841mm

 

 

2m Flue pack

80mm to 1841mm

 

 

3m Flue pack

80mm to 2821mm

 

 

Diagram 4.3

221834B