Goldstar WM-6011, M6003R, M5403R, M5203L, M5203R Possible Trouble, The compressor does not operate

Models: LWC061JGMK1 LWJ0611PCG M5203L M5203R M6003R M5403R WM-6011

1 32
Download 32 pages 48.83 Kb
Page 21
Image 21
• The compressor does not operate.

Possible Trouble 2

• The compressor does not operate.

Is Temp.

setting set lower than Room NO Temp.-0.5°C?

YES

• Set the Temp. setting to higher Temp.

Is the voltage No.11

NO

 

of IC01M 0V?

 

YES

Check the RY-COMP.

Check the wiring Diagram.

 

Is the voltage N0.6 of

 

NO

 

 

 

 

IC01M DC 5V?

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

• Exchange IC01M.

 

 

 

 

 

 

 

 

 

 

 

 

Is the Unit for 3 minutes

delay?

YES

• Wait 3 Minutes

Exchange MAIN P.W.B Ass'y.

NO

Possible Trouble 3

• The compressor always operate.

 

 

Is the wire connection of

RY-COMP all right?

YES

• Check the RY-COMP.

Possible Trouble 4

NO

• Fan does not operate.

Connect LEAD Wire to Manual background RY-COMP again.

Is the voltage NO.2 or 4

NO

of IC01M DC 5V?

 

 

YES

 

 

 

Is the voltage NO.13 or 15

NO

 

of IC01M 0V?

 

YES

Check the RY-Hi or RY-Lo.

Check the wiring diagram.

• Exchange IC01M.

• Exchange IC01M.

— 21—