1.2 SPECIFICATIONS
MODELS | M5403R |
| M5203R |
| M5203L | M6003R | LWJ0611PCG |
ITEMS |
|
| LWC061JGMK1 | ||||
|
|
|
|
| |||
|
|
|
|
|
|
|
|
COOLING CAPACITY (BTU/h) | 5,300 |
| 5,200 |
| 5,200 | 6,000 | 6,000 |
|
|
|
|
|
|
|
|
POWER SUPPLY (Phase, V, Hz) |
|
|
|
| 1ø, 115V, 60HZ |
|
|
|
|
|
|
|
|
|
|
INPUT (W) |
| 530 |
| 470 | 610 | 620 | |
|
|
|
|
|
|
|
|
OPERATING CURRENT (AMP.) |
| 4.8 |
| 4.3 | 5.6 | 5.8 | |
|
|
|
|
|
|
|
|
REFRIGERANT CONTROL |
|
|
| CAPILLARY TUBE |
| ||
|
|
|
|
|
|
| |
REFRIGERANT CHARGE | 230g (8.1 Oz ) |
| 330g(11.6 Oz) | 335g (11.8 Oz) | 235g (8.3 Oz) | ||
|
|
|
|
|
|
|
|
INSIDE FAN |
|
|
| TURBO |
|
| |
|
|
|
|
|
|
| |
OUTSIDE FAN |
|
| PROPELLER FAN WITH SLINGER RING |
| |||
|
|
|
|
|
|
| |
AIR DISCHARGE |
|
|
| ||||
|
|
|
|
|
|
| |
CHASSIS |
|
|
|
| |||
|
|
|
|
|
| ||
PROTECTOR | • OVERLOAD PROTECTOR FOR COMPRESSOR |
| |||||
• INTERNAL PROTECTOR FOR FAN MOTOR |
| ||||||
|
| ||||||
|
|
|
|
|
|
| |
TEMPERATURE CONTROL |
|
| THERMISTOR |
|
| ||
|
|
|
|
|
| ||
ROTARY SWITCH | 5 POSITIONS (LOW FAN, HIGH FAN, OFF, HIGH COOL, LOW COOL) | ||||||
|
|
|
|
|
|
| |
FAN MOTOR | 6 POLES, 16W |
| 6 POLES, 21.3W | 6 POLES, 24W | 6 POLES, 21.4W | ||
|
|
|
|
|
|
|
|
•NOTE: Specifications are subject to minor change without notice for further improvement.
1.3 SAFETY PRECAUTIONS
1.When servicing, set the POWER of CONTROL BOARD to Off and unplug the power cord.
2.Observe the original lead dress.
If a short circuit is found, replace all parts which have been overheated or damaged by the short cir- cuit.
3.After servicing, make an insulation resistance test to prevent the customer's exposure to shock hazards.
1.4 INSULATION RESISTANCE TEST
1.Unplug the power cord and connect a jumper between 2 pins (black and white).
2.The grounding conductor (green or green and yel- low) is to be open.
3.Measure the resistance value with an ohm meter between the jumpered lead and each exposed metallic part on the equipment at all Mode [except POWER OFF].
4.The value should be over 1 MΩ .