Goldstar M5203R, WM-6011, M6003R, M5403R, M5203L Complaint, Cause, Remedy, Compressor cycles on

Models: LWC061JGMK1 LWJ0611PCG M5203L M5203R M6003R M5403R WM-6011

1 32
Download 32 pages 48.83 Kb
Page 25
Image 25

COMPLAINT

CAUSE

REMEDY

 

 

 

Compressor cycles on

Fan motor

If not running, determine the cause. Replace if

overload

 

required.

 

 

 

 

Condenser air flow

Remove the cabinet, inspect the interior surface

 

restriction

of the condenser. If restricted, clean carefully

 

 

with a vacuum cleaner (do not damage fins) or

 

 

brush. Clean the interior base before

 

 

re-assembling.

 

 

 

 

Condenser fins

If the condenser fins are closed over a large

 

(damaged)

area on the coil surface, head pressures will

 

 

increase, causing the compressor to cycle.

 

 

Straighten the fins or replace the coil.

 

 

 

 

Capacitor

Test the capacitor.

 

 

 

 

Wiring

Check the terminals. If loose, repair or replace.

 

 

 

 

Refrigeration system

Check the system for a restriction.

 

 

 

Insufficient cooling.

Air filter

If restricted, clean or replace.

 

 

 

 

Unit undersized

Determine if the unit is properly sized for the

 

 

area to be cooled.

 

 

 

Excessive noise.

Blower or fan

Check the set screw, or clamp. If loose or miss-

 

 

ing, correct. If the blower or fan is hitting scroll

 

 

or barrier, rearrange the air handling parts.

 

 

 

 

Copper tubing

Remove the cabinet and carefully rearrange the

 

 

tubing not to contact the cabinet,

 

 

compressor, shroud, and barrier.

 

 

 

— 25—