BLOWER PERFORMANCE SPECIFICATIONS

BLOWER PERFORMANCE

(CFM & Temperature Rise vs. External Static Pressure)

Model

 

Tons AC

 

 

 

EXTERNAL STATIC PRESSURE (Inches Water Column)

 

(HeatingAs ShippedSpeed)

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at 0.5"

0.1

 

 

0.2

 

0.3

 

0.4

 

0.5

 

0.6

0.7

0.8

Speed

 

 

 

 

 

 

ESP

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

CFM

CFM

 

T1

2.5

875

 

59

 

793

 

65

736

 

70

674

 

77

592

 

88

556

509

460

GME8

T2

3.5

1,032

 

50

 

965

 

54

914

 

57

861

 

60

810

 

64

756

712

659

T3

1.5

1,217

 

43

 

1,153

 

45

1,098

 

47

1,051

 

49

1,009

 

51

964

918

877

0703BXC*

 

 

 

 

 

 

 

T4

3

1,365

 

38

 

1,313

 

39

1,268

 

41

1,221

 

42

1,172

 

44

1,129

1,086

1,054

 

T5

4

1,549

 

33

 

1,505

 

34

1,460

 

36

1,420

 

37

1,378

 

38

1,350

1,305

1,268

 

T1

2.5

1,268

 

53

 

1,198

 

56

1,151

 

58

1,092

 

61

1,041

 

64

988

932

883

GME8

T2

3.5

1,362

 

49

 

1,305

 

51

1,261

 

53

1,212

 

55

1,170

 

57

1,121

1,074

1,021

T3

3

1,576

 

42

 

1,519

 

44

1,473

 

45

1,426

 

47

1,398

 

48

1,341

1,290

1,252

0905CXC*

 

 

 

 

 

 

T4

4

1,755

 

38

 

1,711

 

39

1,657

 

40

1,627

 

41

1,579

 

42

1,548

1,502

1,463

 

 

 

 

 

 

 

 

T5

5

2,183

 

31

 

2,128

 

31

2,094

 

32

2,060

 

32

2,014

 

33

1,992

1,944

1,847

 

T1

3

1,466

 

58

 

1,415

 

60

1,357

 

63

1,306

 

65

1,248

 

68

1,202

1,144

1,088

GME8

T2

4

1,642

 

52

 

1,596

 

53

1,552

 

55

1,499

 

57

1,449

 

59

1,388

1,352

1,306

T3

2.5

1,750

 

49

 

1,750

 

49

1,707

 

50

1,667

 

51

1,610

 

53

1,574

1,531

1,486

1155CXC*

 

 

 

 

 

 

 

T4

4

1,870

 

46

 

1,805

 

47

1,782

 

48

1,737

 

49

1,701

 

50

1,656

1,606

1,571

 

T5

5

2,297

 

37

 

2,297

 

37

2,224

 

38

2,106

 

40

2,014

 

42

1,896

1,813

1,669

1.CFM in chart is without filters(s). Filters do not ship with this furnace, but must be provided by the installer.

2.All furnaces ship as high speed cooling. Installer must adjust blower cooling speed as needed.

3.For most jobs, about 400 CFM per ton when cooling is desirable.

4.INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.

5.The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. The shaded area indicates ranges in excess of maximum external static pressure allowed when heating. The data for 0.6" w.c. to 0.8" w.c. is shown for air conditioning purposes only.

6 The dashed (---) areas indicate a temperature rise not recommended for this model.

7.The above chart is for U.S. furnaces installed at 0-4000 feet. At higher altitudes, a properly derated unit will have approximately the same temperature rise at a particular CFM, while the ESP at that CFM will be lower.

12

Page 12
Image 12
Goodman Mfg GME8 service manual Blower Performance Specifications