PRoDUcT SPeciFicATionS PRoDUcT SPeciFicATionS
SS-GPC13H www.goodmanmfg.com 15
exPAnDeD cooling DATAgPc1336h41Ac (conT.)
Outdoor Ambient Temperature
65ºF 75ºF 85ºF 95ºF 105ºF 115ºF
Entering Indoor Wet Bulb Temperature
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
80
1350
MBh 35.7 36.5 39.0 41.7 34.9 35.6 38.1 40.7 34.0 34.8 37.2 39.7 33.2 33.9 36.3 38.8 31.5 32.2 34.4 36.8 29.2 29.9 31.9 34.1
S/T 0.93 0.87 0.71 0.53 0.96 0.90 0.73 0.55 1.00 0.92 0.75 0.56 1.00 0.95 0.78 0.58 1.00 1.00 0.81 0.60 1.00 1.00 0.81 0.61
∆T 23 22 19 15 23 22 19 15 23 22 19 15 23 22 19 15 21 22 19 15 20 20 18 14
kW 2.57 2.63 2.71 2.79 2.77 2.82 2.91 3.00 2.93 3.00 3.09 3.19 3.08 3.15 3.25 3.36 3.21 3.28 3.39 3.50 3.32 3.39 3.50 3.62
Amps 11.1 11.3 11.6 12.0 11.8 12.1 12.4 12.8 12.7 12.9 13.3 13.7 13.4 13.7 14.1 14.6 14.2 14.5 14.9 15.4 14.9 15.2 15.7 16.2
HI PR 246 265 280 292 276 297 314 327 314 338 357 372 358 385 407 424 403 433 458 477 445 479 505 527
LO PR 110 117 128 136 116 124 135 144 121 128 140 149 127 135 147 157 133 141 154 164 137 146 160 170
1200
MBh 34.7 35.4 37.8 40.5 33.9 34.6 37.0 39.5 33.0 33.8 36.1 38.6 32.2 32.9 35.2 37.6 30.6 31.3 33.4 35.7 28.4 29.0 31.0 33.1
S/T 0.88 0.83 0.67 0.50 0.92 0.86 0.70 0.52 0.94 0.88 0.72 0.54 0.97 0.91 0.74 0.55 1.00 0.94 0.77 0.57 1.00 0.95 0.77 0.58
∆T 23 22 20 16 24 23 20 16 24 23 20 16 24 23 20 16 23 23 20 16 22 21 18 15
kW 2.55 2.61 2.69 2.77 2.74 2.80 2.89 2.98 2.91 2.97 3.07 3.17 3.06 3.12 3.22 3.33 3.18 3.25 3.36 3.47 3.29 3.36 3.47 3.59
Amps 11.0 11.2 11.5 11.9 11.7 12.0 12.3 12.7 12.6 12.8 13.2 13.6 13.3 13.6 14.0 14.4 14.1 14.4 14.8 15.3 14.8 15.1 15.5 16.1
HI PR 244 262 277 289 274 294 311 324 311 335 354 369 354 381 403 420 399 429 453 472 440 474 500 522
LO PR 109 116 126 135 115 122 134 142 120 127 139 148 126 134 146 155 132 140 153 163 136 145 158 168
1050
MBh 32.0 32.7 34.9 37.3 31.2 31.9 34.1 36.5 30.5 31.2 33.3 35.6 29.8 30.4 32.5 34.7 28.3 28.9 30.9 33.0 26.2 26.8 28.6 30.6
S/T 0.85 0.80 0.65 0.49 0.88 0.83 0.67 0.50 0.91 0.85 0.69 0.52 0.93 0.88 0.71 0.53 0.97 0.91 0.74 0.55 0.98 0.92 0.75 0.56
∆T 24 23 20 16 24 23 20 16 24 23 20 16 24 23 20 16 24 23 20 16 22 21 19 15
kW 2.50 2.55 2.62 2.70 2.68 2.73 2.82 2.91 2.84 2.90 2.99 3.09 2.98 3.05 3.15 3.25 3.11 3.17 3.28 3.38 3.21 3.28 3.39 3.50
Amps 10.7 11.0 11.3 11.6 11.5 11.7 12.0 12.4 12.3 12.5 12.9 13.3 13.0 13.3 13.7 14.1 13.7 14.0 14.4 14.9 14.4 14.7 15.2 15.7
HI PR 236 254 269 280 265 286 302 314 302 325 343 358 344 370 391 407 387 416 439 458 427 460 485 506
LO PR 106 112 123 131 112 119 130 138 116 123 135 143 122 130 141 151 128 136 148 158 132 140 153 163
85
1350
MBh 36.3 37.0 38.8 41.4 35.5 36.2 37.9 40.4 34.6 35.3 37.0 39.4 33.8 34.4 36.1 38.5 32.1 32.7 34.3 36.6 29.7 30.3 31.7 33.9
S/T 0.97 0.94 0.85 0.69 1.00 0.97 0.88 0.71 1.00 1.00 0.90 0.73 1.00 1.00 0.93 0.75 1.00 1.00 0.96 0.78 1.00 1.00 0.97 0.79
∆T 24 24 22 19 24 24 23 20 24 24 23 20 23 23 23 20 22 22 22 19 20 21 21 18
kW 2.59 2.65 2.73 2.81 2.79 2.85 2.93 3.03 2.96 3.02 3.12 3.22 3.11 3.18 3.28 3.38 3.24 3.31 3.41 3.53 3.35 3.42 3.53 3.65
Amps 11.2 11.4 11.7 12.1 11.9 12.2 12.5 12.9 12.8 13.0 13.4 13.9 13.5 13.8 14.2 14.7 14.3 14.6 15.0 15.5 15.0 15.3 15.8 16.3
HI PR 249 268 283 295 279 300 317 331 317 342 361 376 361 389 411 428 407 438 462 482 449 483 511 533
LO PR 111 118 129 137 117 125 136 145 122 130 142 151 128 136 149 158 134 143 156 166 139 148 161 172
1200
MBh 35.3 35.9 37.7 40.2 34.4 35.1 36.8 39.2 33.6 34.3 35.9 38.3 32.8 33.4 35.0 37.4 31.2 31.8 33.3 35.5 28.9 29.4 30.8 32.9
S/T 0.93 0.89 0.81 0.65 0.96 0.93 0.84 0.68 0.98 0.95 0.86 0.70 1.00 0.98 0.89 0.72 1.00 1.00 0.92 0.75 1.00 1.00 0.93 0.75
∆T 25 25 23 20 25 25 24 20 25 25 24 20 25 25 24 21 24 24 23 20 22 23 22 19
kW 2.57 2.63 2.71 2.79 2.77 2.82 2.91 3.00 2.93 3.00 3.09 3.19 3.08 3.15 3.25 3.36 3.21 3.28 3.39 3.50 3.32 3.39 3.50 3.62
Amps 11.1 11.3 11.6 12.0 11.8 12.1 12.4 12.8 12.7 12.9 13.3 13.7 13.4 13.7 14.1 14.6 14.2 14.5 14.9 15.4 14.9 15.2 15.7 16.2
HI PR 246 265 280 292 276 297 314 327 314 338 357 372 358 385 407 424 403 433 458 477 445 479 505 527
LO PR 110 117 128 136 116 124 135 144 121 128 140 149 127 135 147 157 133 141 154 164 137 146 160 170
1050
MBh 32.6 33.2 34.8 37.1 31.8 32.4 33.9 36.2 31.0 31.6 33.1 35.4 30.3 30.9 32.3 34.5 28.8 29.3 30.7 32.8 26.6 27.2 28.4 30.3
S/T 0.89 0.86 0.78 0.63 0.93 0.89 0.81 0.65 0.95 0.92 0.83 0.67 0.98 0.95 0.85 0.69 1.00 0.98 0.89 0.72 1.00 0.99 0.89 0.72
∆T 25 25 24 20 26 25 24 21 26 25 24 21 26 26 24 21 25 25 24 21 23 24 22 19
kW 2.51 2.57 2.64 2.73 2.70 2.76 2.84 2.93 2.86 2.92 3.02 3.11 3.01 3.07 3.17 3.27 3.13 3.20 3.30 3.41 3.24 3.31 3.42 3.53
Amps 10.8 11.0 11.3 11.7 11.5 11.8 12.1 12.5 12.4 12.6 13.0 13.4 13.1 13.4 13.8 14.2 13.8 14.1 14.5 15.0 14.5 14.8 15.3 15.8
HI PR 239 257 271 283 268 288 305 318 305 328 346 361 347 374 394 411 391 420 444 463 431 464 490 511
LO PR 107 113 124 132 113 120 131 139 117 125 136 145 123 131 143 152 129 137 150 159 133 142 155 165
IDB: Entering Indoor Dry Bulb Temperature Shaded area reects AHRI (TVA) condions. kW = Total system power
High and low pressures are measured at the liquid and sucon service valves. Amps = outdoor unit amps (comp.+fan)