Product Specifications
Specifications
GPC13
24H41AC
GPC13
30H41AA
GPC13
30H41AC
GPC13
36H41AA
GPC13
36H41AC
Cooling Capacity
Total BTU/h
Sensible BTU/h
SEER / EER
Decibels
AHRI #
24,000 | 28,600 | 28,600 | 36,000 | 36,000 |
18,600 | 22,700 | 22,700 | 26,000 | 26,000 |
13.0 / 11.0 | 13.0 / 11.0 | 13.0 / 11.0 | 13.0 / 11.0 | 13.0 / 11.0 |
76 | 76 | 76 | 78 | 78 |
4635457 | 4635469 | 4635458 | 4635470 | 4635459 |
|
|
|
|
|
Evaporator Motor
Type | PSC | PSC | PSC | PSC | PSC |
|
|
|
|
|
|
Wheel (D x W) | 9 x 6 | 9 x 6 | 9 x 6 | 9 x 8 | 9 x 8 |
|
|
|
|
|
|
Nominal Cooling CFM | 815 | 1,080 | 1,080 | 1,205 | 1,205 |
|
|
|
|
|
|
RLA / LRA | 1.5 / 2.2 | 1.86 / 3.2 | 1.86 / 3.2 | 1.86 / 3.2 | 1.86 / 3.2 |
|
|
|
|
|
|
No. of Speeds | 3 | 3 | 3 | 3 | 3 |
|
|
|
|
|
|
Horsepower - RPM | ¼ - 952 | ⅓ - 1,020 | ⅓ - 1,020 | ⅓ - 1,020 | ⅓ - 1,020 |
|
|
|
|
|
|
Evaporator Coil |
|
|
|
|
|
|
|
|
|
|
|
Face Area (ft²) | 4.6 | 4.6 | 4.6 | 5.2 | 5.2 |
|
|
|
|
|
|
Rows Deep / Fins per Inch | 3 / 14 | 3 / 14 | 3 / 14 | 3 / 14 | 3 / 14 |
|
|
|
|
|
|
Filter Size (“) | 20 x 20 x 1 | 20 x 25 x 1 | 20 x 25 x 1 | 25 x 25 x 1 | 25 x 25 x 1 |
|
|
|
|
|
|
Drain Size (NPT) | ¾" | ¾" | ¾" | ¾" | ¾" |
|
|
|
|
|
|
Refrigerant Charge (oz.) | 63 | 80 | 62 | 85 | 61 |
|
|
|
|
|
|
Condenser Fan / Coil |
|
|
|
|
|
|
|
|
|
|
|
Horsepower - RPM | ¹/6 - 815 | ¼ - 830 | ¹/6 - 815 | ¼ - 830 | ¼ - 830 |
|
|
|
|
|
|
RLA / LRA | 1.1 / 1.7 | 1.5 / 3.0 | 1.1 / 1.7 | 1.5 / 3.0 | 1.5 / 3.0 |
|
|
|
|
|
|
Fan Diameter/ # Fan Blades | 22 / 2 | 22 / 3 | 22 /2 | 22 /4 | 22 / 4 |
|
|
|
|
|
|
Face Area (ft²) | 12.3 | 13.4 | 12.3 | 13.4 | 12.3 |
|
|
|
|
|
|
Rows Deep / Fins per Inch | 1 / 26 | 1 / 24 | 1 / 26 | 1 / 24 | 1 / 26 |
|
|
|
|
|
|
Compressor |
|
|
|
|
|
|
|
|
|
|
|
Quantity | 1 | 1 | 1 | 1 | 1 |
|
|
|
|
|
|
Type | Scroll | Recip | Scroll | Scroll | Scroll |
|
|
|
|
|
|
Stage | Single | Single | Single | Single | Single |
|
|
|
|
|
|
Compressor RLA / LRA | 13.5 / 58.3 | 9.8 / 55 | 12.8 / 64 | 16.7 / 79 | 16.7 / 79 |
|
|
|
|
|
|
Electrical Data |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Indoor Blower FLA | 1.5 | 1.86 | 1.86 | 1.86 | 1.86 |
|
|
|
|
|
|
Outdoor Fan RLA | 1.7 | 1.5 | 1.7 | 1.5 | 1.5 |
|
|
|
|
|
|
Total Unit Amps | 16.1 | 13.16 | 15.76 | 20.06 | 20.06 |
|
|
|
|
|
|
Min. Circuit Ampacity¹ | 19.5 | 15.6 | 19 | 24.2 | 24.2 |
|
|
|
|
|
|
Max. Overcurrent Protection (amps)² | 30 | 25 | 30 | 40 | 40 |
|
|
|
|
|
|
Ship Weight (lbs) | 290 | 310 | 290 | 370 | 370 |
|
|
|
|
|
|
¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or
Note: Always check the S&R plate for electrical data on the unit being installed.
www.goodmanmfg.com | 3 |