PRoDUcT SPeciFicATionS PRoDUcT SPeciFicATionS
SS-GPC13H www.goodmanmfg.com 5
AiRFlow DATA
Model Motor
Speed Volts E.S.P (In. of H2O)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
GPC13
24H41**
Low 230 CFM 680 640 590 555 505 440 340 -
Was 155 150 145 140 130 120 110 -
Med 230 CFM 895 855 815 755 700 630 545 390
Was 230 220 215 205 195 180 170 145
High 230 CFM 1,185 1,130 1,070 1,010 930 850 760 650
Was 350 340 325 310 295 280 265 245
GPC13
30H41**
Low 230 CFM 1,150 1,080 1,025 975 925 845 - -
Was 340 330 315 305 295 280 - -
Med 230 CFM 1,335 1,275 1,205 1,135 1,075 985 910 845
Was 425 415 400 385 370 350 330 310
High 230 CFM 1,435 1,355 1,280 1,200 1,120 1,030 950 875
Was 485 465 455 435 415 400 385 370
GPC13
36H41**
Low 230 CFM 1,180 1,125 1,075 1,020 955 875 655 -
Was 335 325 315 305 295 275 240 -
Med 230 CFM 1,350 1,280 1,205 1,130 1,050 985 910 845
Was 435 420 405 385 375 350 330 310
High 230 CFM 1,450 1,370 1,290 1,205 1,130 1,040 960 885
Was 495 480 465 440 425 400 385 370
GPC13
42H41**/
GPC13
49H41**
Low 230 CFM 1,425 1,410 1,355 1,310 1,245 1,170 1,080 -
Was 450 445 430 420 405 390 370 -
Med 230 CFM 1,620 1,595 1,545 1,485 1,425 1,345 1,250 1,160
Was 550 540 525 510 495 475 450 425
High 230 CFM 1,945 1,935 1,875 1,800 1,730 1,635 1,535 1,440
Was 765 755 735 715 695 670 640 615
GPC13
48H41**
Low 230 CFM 1,425 1,410 1,355 1,310 1,245 1,170 1,080 -
Was 450 445 430 420 405 390 370 -
Med 230 CFM 1,720 1,660 1,585 1,520 1,460 1,365 1,270 -
Was 560 555 540 530 520 490 470 -
High 230 CFM 2,110 2,060 1,980 1,895 1,795 1,705 1,590 1,500
Was 785 780 765 745 720 705 665 625
GPC13
60H41**
“T” 1
Low 230 CFM 1,775 1,635 1,645 1,515 1,510 1,450 1,430 1,400
Was 395 420 435 445 455 465 470 475
“T” 2
Med 230 CFM 1,845 1,790 1,715 1,685 1,590 1,580 1,530 1,500
Was 490 505 520 535 550 560 570 575
“T” 3
High 230 CFM 2,025 1,900 1,840 1,780 1,725 1,650 1,620 1,580
Was 575 595 620 630 645 655 660 670
Notes
Data shown is dry coil; wet coil pressure drop is approximate.
0.1” H2O, for 2-row indoor coil; 0.2” H2O, for 3-row indoor coil; and 0.3” H2O, for 4-row indoor coil
Data shown does not include lter pressure drop, approx. 0.08” H2O.
ALL MODELS SHOULD RUN NO LESS THAN 350 CFM / TON, USE HIGHER SPEED TAP OR NEXT SIZE LARGER BLOWER ASM.
See Repair Parts list.
Reduce airow by 2% for 208V operaon.