PRoDUcT SPeciFicATionS PRoDUcT SPeciFicATionS
SS-GPC13H www.goodmanmfg.com 5
AiRFlow DATAModel Motor
Speed Volts E.S.P (In. of H2O)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
GPC13
24H41**
Low 230 CFM 680 640 590 555 505 440 340 -
Was 155 150 145 140 130 120 110 -
Med 230 CFM 895 855 815 755 700 630 545 390
Was 230 220 215 205 195 180 170 145
High 230 CFM 1,185 1,130 1,070 1,010 930 850 760 650
Was 350 340 325 310 295 280 265 245
GPC13
30H41**
Low 230 CFM 1,150 1,080 1,025 975 925 845 - -
Was 340 330 315 305 295 280 - -
Med 230 CFM 1,335 1,275 1,205 1,135 1,075 985 910 845
Was 425 415 400 385 370 350 330 310
High 230 CFM 1,435 1,355 1,280 1,200 1,120 1,030 950 875
Was 485 465 455 435 415 400 385 370
GPC13
36H41**
Low 230 CFM 1,180 1,125 1,075 1,020 955 875 655 -
Was 335 325 315 305 295 275 240 -
Med 230 CFM 1,350 1,280 1,205 1,130 1,050 985 910 845
Was 435 420 405 385 375 350 330 310
High 230 CFM 1,450 1,370 1,290 1,205 1,130 1,040 960 885
Was 495 480 465 440 425 400 385 370
GPC13
42H41**/
GPC13
49H41**
Low 230 CFM 1,425 1,410 1,355 1,310 1,245 1,170 1,080 -
Was 450 445 430 420 405 390 370 -
Med 230 CFM 1,620 1,595 1,545 1,485 1,425 1,345 1,250 1,160
Was 550 540 525 510 495 475 450 425
High 230 CFM 1,945 1,935 1,875 1,800 1,730 1,635 1,535 1,440
Was 765 755 735 715 695 670 640 615
GPC13
48H41**
Low 230 CFM 1,425 1,410 1,355 1,310 1,245 1,170 1,080 -
Was 450 445 430 420 405 390 370 -
Med 230 CFM 1,720 1,660 1,585 1,520 1,460 1,365 1,270 -
Was 560 555 540 530 520 490 470 -
High 230 CFM 2,110 2,060 1,980 1,895 1,795 1,705 1,590 1,500
Was 785 780 765 745 720 705 665 625
GPC13
60H41**
“T” 1
Low 230 CFM 1,775 1,635 1,645 1,515 1,510 1,450 1,430 1,400
Was 395 420 435 445 455 465 470 475
“T” 2
Med 230 CFM 1,845 1,790 1,715 1,685 1,590 1,580 1,530 1,500
Was 490 505 520 535 550 560 570 575
“T” 3
High 230 CFM 2,025 1,900 1,840 1,780 1,725 1,650 1,620 1,580
Was 575 595 620 630 645 655 660 670
Notes
• Data shown is dry coil; wet coil pressure drop is approximate.
• 0.1” H2O, for 2-row indoor coil; 0.2” H2O, for 3-row indoor coil; and 0.3” H2O, for 4-row indoor coil
• Data shown does not include lter pressure drop, approx. 0.08” H2O.
• ALL MODELS SHOULD RUN NO LESS THAN 350 CFM / TON, USE HIGHER SPEED TAP OR NEXT SIZE LARGER BLOWER ASM.
See Repair Parts list.
• Reduce airow by 2% for 208V operaon.