Product Specifications
Product Specifications — CPG048 B Models
CPG048
0901DXXX
CPG048
0903DXXX
CPG048
0903BXXX
CPG048
0904BXXX
Cooling Capacity
Total BTU/h | 45,500 | 45,500 | 45,500 | 45,500 |
Sensible BTU/h | 35,000 | 35,000 | 35,000 | 35,000 |
SEER / EER | 13.0 / 11.3 | 13.0 / 11.3 | 13.0 / 11.3 | 13.0 / 11.3 |
Decibels | 78 | 78 | 78 | 78 |
AHRI Reference #s | 4385062 | 4385063 | 4385063 | 4385064 |
Heating Capacity |
|
|
|
|
Max. Input /Output kBTU/h | 92 / 74 | 92 / 74 | 92 / 74 | 92 / 74 |
Low Input /Output kBTU/h | 69 / 55 | 69 / 55 | 69 / 55 | 69 / 55 |
Steady State Efficiency (AFUE) | 80 | 80 | 80 | 80 |
Temperature Rise Range (°F) Hi / Low | ||||
No. of Burners | 4 | 4 | 4 | 4 |
Evaporator Motor / Coil |
|
|
|
|
|
|
|
|
|
Motor Type | Direct Drive | Direct Drive | Belt Drive | Belt Drive |
Indoor Nominal CFM | 1,600 | 1,600 | 1,600 | 1,600 |
Motor Speed Tap (Cooling) | Medium | Medium | ||
|
|
|
|
|
Indoor Motor FLA (Cooling) | 2.87 | 2.87 | 3.8 | 1.9 |
Horsepower - RPM | ½ - 1,000 | ½ - 1,000 | 1.0 / 1,725 | 1.0 / 1,725 |
|
|
|
|
|
Piston Size (Cooling) | 0.076 | 0.076 | 0.076 | 0.076 |
Filter Size (#) | 14 x 20 x 2 (4) | 14 x 20 x 2 (4) | 14 x 20 x 2 (4) | 14 x 20 x 2 (4) |
Drain Size (NPT) | ¾” | ¾” | ¾” | ¾” |
|
|
|
|
|
103 | 103 | 105 | 103 | |
Evaporator Coil Face Area (ft²) | 7.0 | 7.0 | 7.0 | 7.0 |
|
|
|
|
|
Rows Deep / Fins per Inch | 4 / 16 | 4 / 16 | 4 / 16 | 4 / 16 |
Belt Drive Evap Fan Data |
|
|
|
|
# of Wheels (D” x W”) | (1) 11 x 10 | (1) 11 x 10 | ||
|
|
|
|
|
Motor Sheave / Blower Sheave | VL44 X ⅝ / AK66 X 1 | |||
Belt | AX55 | AX55 | ||
|
|
|
|
|
Condenser Fan / Coil |
|
|
|
|
Quantity of Condenser Fan Motors | 1 | 1 | 1 | 1 |
Horsepower - RPM | ¼ - 1,090 | ¼ - 1,090 | ¼ - 1,090 | ¼ - 890 |
|
|
|
|
|
Fan Diameter / # Fan Blades | 22 / 4 | 22 / 4 | 22 / 4 | 22 / 4 |
Outdoor Nominal CFM | 3,800 | 3,800 | 3,800 | 3,800 |
|
|
|
|
|
Face Area (ft²) | 17.0 | 17.0 | 17.0 | 17.0 |
Rows Deep / Fins per Inch | 1 / 24 | 1 / 24 | 1 / 24 | 1 / 24 |
Compressor |
|
|
|
|
|
|
|
|
|
Quantity / Stage | 1 / Single | 1 / Single | 1 / Single | 1 / Single |
Type | Scroll | Scroll | Scroll | Scroll |
|
|
|
|
|
Compressor RLA / LRA | 19.9 / 109 | 13.1 / 83.1 | 13.1 / 83.1 | 6.1 / 41 |
Electrical Data |
|
|
|
|
|
|
|
|
|
Outdoor Fan FLA | 1.40 | 1.40 | 1.40 | 0.80 |
Total Unit Amps | 24.1 | 17.4 | 18.3 | 8.8 |
|
|
|
|
|
Min. Circuit Ampacity¹ | 29 | 21 | 22 | 10 |
Max. Overcurrent Protection (amps)² | 45 | 30 | 30 | 15 |
|
|
|
|
|
Power Supply Conduit Hole | 1.125 | 1.125 | 1.125 | 1.125 |
|
|
|
|
|
½” | ½” | ½” | ½” | |
Operating Weight (lbs) | 575 | 575 | 575 | 575 |
|
|
|
|
|
Ship Weight (lbs) | 600 | 600 | 600 | 600 |
¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or
Note: Always check the S&R plate for electrical data on the unit being installed.
www.goodmanmfg.com | 5 |