Product Specifications
Product Specifications — CPG072 B Models
CPG072
1403BXXX
CPG072
1404BXXX
CPG072
1407BXXX
Cooling Capacity
Total BTU/h
Sensible BTU/h
EER
Decibels
AHRI Number
Heating Capacity
71,000 | 71,000 | 71,000 |
48,280 | 48,280 | 48,280 |
11.1 | 11.1 | 11.1 |
78.0 | 78.0 | 78.0 |
3397632 | 3397632 | 3397632 |
|
|
|
Max. Input / Output KBTU/h | 138 / 110.4 | 138 / 110.4 | 138 / 110.4 |
Low Input/ Output KBTU/h | 103 / 83 | 103 / 83 | 103 / 83 |
|
|
|
|
Steady State Efficiency | 80 | 80 | 80 |
|
|
|
|
Temperature Rise Range (°F) | |||
|
|
|
|
No. of Burners | 6 | 6 | 6 |
|
|
|
|
Evaporator Motor / Coil |
|
|
|
|
|
|
|
Motor Type | Belt Drive | Belt Drive | Belt Drive |
|
|
|
|
# of Wheels (D x W) | 1 (11" x 10") | 1 (11" x 10") | 1 (11" x 10") |
Indoor Nominal CFM | 2,400 | 2,400 | 2,400 |
Indoor Motor FLA (Cooling) | 5.0 | 2.5 | 2.3 |
Horsepower - RPM | |||
Piston Size (Cooling) | 0.094 | 0.094 | t |
Filter Size (Qty) | (4) 16" x 20" x 2" | (4) 16" x 20" x 2" | (4) 16" x 20" x 2" |
Drain Size (NPT) | ¾" | ¾" | ¾" |
213.0 | 213.0 | 213.0 | |
|
|
|
|
Evaporator Coil Face Area (ft²) | 8.9 | 8.9 | 8.9 |
|
|
|
|
Rows Deep/ Fins per Inch | 4/ 16 | 4/ 16 | 4/ 16 |
|
|
|
|
Motor Sheave | VL44 x 7/8 | VL44 x 7/8 | VL44 x 7/8 |
|
|
|
|
Blower Sheave / Belt | AK59x1 / AX53 | AK59x1 / AX53 | AK59x1 / AX53 |
|
|
|
|
Condenser Fan / Coil |
|
|
|
Quantity of Condenser Fan Motors | 1 | 1 | 1 |
Horsepower - RPM | ⅓ - 1,075 | ⅓ - 1,075 | ⅓ - 1,075 |
Fan Diameter/ # Fan Blades | 22/ 4 | 22/ 4 | 22/ 4 |
Outdoor Nominal CFM | 4,300 | 4,300 | 4,300 |
Face Area (ft²) | 18.7 | 18.7 | 18.7 |
Rows Deep/ Fins per Inch | 2/ 20 | 2/ 20 | 2/ 20 |
Compressor |
|
|
|
|
|
|
|
Quantity / Stage | 1 / Single | 1 / Single | 1 / Single |
|
|
|
|
Type | Scroll | Scroll | Scroll |
|
|
|
|
Compressor RLA / LRA | 19/ 123 | 9.7/ 62 | 7.4/ 50 |
|
|
|
|
Electrical Data |
|
|
|
|
|
|
|
Voltage/ Phase/ Frequency | 460/ 3/ 60 | 575/ 3/ 60 | |
1.0 | 1.0 | 1.0 | |
Outdoor Fan FLA | 1.90 | 1.20 | 0.90 |
Total Unit Amps | 25.9 | 13.4 | 10.6 |
Min. Circuit Ampacity¹ | 31 | 16 | 12 |
Max. Overcurrent Protection (amps)² | 45 | 25 | 15 |
Entrance Power Supply | 1.125" | 1.125” | 1.125” |
Entrance Control Voltage | ½" | ½" | ½" |
Operating Weight (lbs) | 690 | 690 | 690 |
Ship Weight (lbs) | 715 | 715 | 715 |
¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or
Note: Always check the S&R plate for electrical data on the unit being installed.
www.goodmanmfg.com | 9 |