Goodman Mfg SS-CPG36-72 warranty Product Specifications - CPG060 B Models

Models: SS-CPG36-72

1 40
Download 40 pages 7.92 Kb
Page 7
Image 7
Product Specifications — CPG060 B Models

Product Specifications

Product Specifications — CPG060 B Models

CPG060

0901DXXX

CPG060

0903DXXX

CPG060

0903BXXX

CPG060

0904BXXX

Cooling Capacity

Total BTU/h

59,500

59,500

59,500

59,500

Sensible BTU/h

43,200

43,200

43,200

43,200

SEER / EER

13 / 11.3

13 / 11.3

13 / 11.3

13 / 11.3

Decibels

78

78

78

78

ARI Reference Nos.

4385065

4385066

4385066

4385067

Gas Heating Capacity

 

 

 

 

 

 

 

 

 

Max. Input /Output kBTU/h

92 / 74

92 / 74

92 / 74

92 / 74

 

 

 

 

 

Low Input /Output kBTU/h

69 / 55

69 / 55

69 / 55

69 / 55

 

 

 

 

 

Steady State Efficiency (AFUE)

80

80

80

80

 

 

 

 

 

Temperature Rise Range (°F)

20-50 / 15-45

20-50 / 15-45

20-50 / 15-45

20-50 / 15-45

 

 

 

 

 

No. of Burners

4

4

4

4

 

 

 

 

 

Evaporator Motor / Coil

 

 

 

 

Motor Type

Direct

Direct

Belt

Belt

Indoor Nominal CFM

2,000

2,000

2,000

2,000

Piston Size (Cooling)

0.086

0.086

0.086

0.086

Filter Size (#)

14 x 20 x 2 (4)

14 x 20 x 2 (4)

14 x 20 x 2 (4)

14 x 20 x 2 (4)

Drain Size (NPT)

¾”

¾”

¾”

¾”

R-410A Refrigerant Charge (oz.)

162

162

162

165

 

 

 

 

 

Face Area (ft²)

7.8

7.8

7.8

7.8

 

 

 

 

 

Rows Deep/ Fins per Inch

4 / 16

4 / 16

4 / 16

4 / 16

 

 

 

 

 

Tube Diameter - Material

5/16 - Copper

5/16 - Copper

5/16 - Copper

5/16 - Copper

 

 

 

 

 

Belt Drive Evap Fan Data

 

 

 

 

 

 

 

 

 

# of Wheels (D x W)

---

---

1 (11” x 10”)

1 (11” x 10”)

 

 

 

 

 

Motor Sheave / Blower Sheave

---

---

VL44 X ⅝ / AK61 X 1

Belt

---

---

AX53

AX53

Condenser Fan / Coil

 

 

 

 

Horsepower / RPM

¼ / 1,090

¼ / 1,090

¼ / 1,090

¼ / 1,090

Fan Diameter/ # Fan Blades

22 / 4

22 / 4

22 / 4

22 / 4

Outdoor Nominal CFM

3,800

3,800

3,800

3,800

Face Area (ft²)

17.0

17.0

17.0

17.0

Rows Deep/ Fins per Inch

2 / 18

2 / 18

2 / 18

2 / 18

 

 

 

 

 

Tube Diameter - Material

5/16 - Copper

5/16 - Copper

5/16 - Copper

5/16 - Copper

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

Quantity / Stage

1 / Single

1 / Single

1 / Single

1 / Single

 

 

 

 

 

Type

Scroll

Scroll

Scroll

Scroll

Compressor RLA / LRA

26.4 / 134

16 / 110

16 / 110

7.8 / 52

Electrical Data

 

 

 

 

Voltage-Phase-Frequency

208/230-1-60

208/230-3-60

208/230-3-60

460-3-60

Indoor Blower HP / FLA )STD Static)

1.0 / 7.6

1.0 / 7.6

1.0 / 3.8

1.0 / 1.9

Indoor Blower LRA

----

----

24

13

Outdoor Fan HP / FLA

¼ / 1.40

¼ / 1.40

¼ / 1.40

¼ / 0.8

Min. Circuit Ampacity¹

42

29

25

13

Max. Overcurrent Protection (amps)²

60

45

40

20

Power Supply Conduit Hole

1.125

1.125

1.125

1.125

Low-Voltage Conduit Hole

½”

½”

½”

½”

Operating Weight (lbs)

620

620

620

620

Ship Weight (lbs)

645

645

645

645

¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted.

Note: Always check the S&R plate for electrical data on the unit being installed.

SS-CPG36-72

www.goodmanmfg.com

7

Page 7