Adequate clearance around the unit should be kept for safety, service, maintenance, and proper unit operation. A total clear- ance of 75” on the main control panel side of the unit is rec- ommended to facilitate possible fan shaft, coil, electric heat and gas furnace removal. A clearance of 48” is recommended on all other sides of the unit to facilitate possible compressor removal, to allow service access and to insure proper venti- lation and condenser airflow. The unit must not be installed beneath any obstruction. The unit should be installed re- mote from all building exhausts to inhibit ingestion of exhaust air into the unit fresh air intake.

INSULATED

PANELS

Roof Curb Installation

ROOF CURB POST-INSTALLATION CHECKS

After installation, check the top of the curb, duct connection frame and duct flanges to make sure gasket has been ap- plied properly. Gasket should be firmly applied to the top of the curb perimeter, duct flanges and any exposed duct con- nection frame. If gasket is loose, re-apply using strong weather resistant adhesive.

PROTRUSION

Inspect curb to ensure that none of the utility services (elec- tric) routed through the curb protrude above the curb.

CAUTION

IF PROTRUSIONS EXIST, DO NO ATTEMPT TO SET UNIT ON CURB.

ROOF TOP DUCT CONNECTIONS

Install all duct connections on the unit before placing the unit on rooftop.

HORIZONTAL DISCHARGE

For horizontal discharge, remove the supply and return duct covers and place them over the vertical discharge return and supply openings. Install with insulation facing up, using the longer screws provided in the literature package.

Ensure that the top of the duct connection frame is flush with the top of the roof curb.

Flexible duct connectors between the unit and ducts are rec- ommended. Insulate and weatherproof all external ductwork and joints as required and in accordance with local codes.

 

 

11”

4 7/8”

 

REMOVE

 

 

 

COVERS

 

 

 

17”

7 3/8”

 

 

 

 

25”

12”

SUPPLY

 

 

6 3/16”

 

 

Horizontal Discharge Duct Connections

6

Page 6
Image 6