A |
| C |
|
| RETURN |
Y | CONDENSER |
|
|
| |
| COIL | EVAPORATOR COIL |
|
| |
|
| CG |
|
| SUPPLY |
B | COMPRESSOR | D |
| ||
| X |
|
Corner & Center of Gravity Locations
Model | X | Y | Shipping | Operating |
| Corner Weights ( lbs ) |
| |||
(in) | (in) | Weight | Weight |
|
|
|
|
|
| |
A |
| B | C |
| D | |||||
| (lbs) | (lbs) |
|
| ||||||
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
| |
CPG036045* | 37 | 30 | 550 | 525 | 100 |
| 165 | 100 |
| 165 |
|
|
|
|
|
|
|
|
|
|
|
CPG036090* | 37 | 30 | 560 | 535 | 100 |
| 170 | 100 |
| 170 |
|
|
|
|
|
|
|
|
|
|
|
CPG048090* | 37 | 30 | 600 | 575 | 110 |
| 180 | 110 |
| 180 |
|
|
|
|
|
|
|
|
|
|
|
CPG048115* | 37 | 30 | 605 | 580 | 110 |
| 180 | 110 |
| 180 |
|
|
|
|
|
|
|
|
|
|
|
CPG060090* | 37 | 30 | 645 | 620 | 115 |
| 190 | 120 |
| 195 |
|
|
|
|
|
|
|
|
|
|
|
CPG060140* | 37 | 30 | 655 | 630 | 120 |
| 195 | 120 |
| 195 |
|
|
|
|
|
|
|
|
|
|
|
CPG072140* | 37 | 30 | 715 | 690 | 130 |
| 215 | 130 |
| 215 |
|
|
|
|
|
|
|
|
|
|
|
* Weights shown are belt drive with no accessories.
CAUTION
TO PREVENT SEVERE DAMAGE TO THE BOTTOM OF THE UNIT, DO NOT
FORK LIFT UNIT AFTER WOOD STRUTS HAVE BEEN REMOVED.
Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, care should be taken to center the unit. Check for proper alignment and orientation of supply and return openings with duct.
RIGGING REMOVAL
CAUTION
TO PREVENT DAMAGE TO THE UNIT, DO NOT ALLOW CRANE HOOKS
AND SPREADER BARS TO REST ON THE ROOF OF THE UNIT.
Remove spreader bars, lifting cables and other rigging equipment.
8