A

 

C

 

 

RETURN

Y

CONDENSER

 

 

 

 

COIL

EVAPORATOR COIL

 

 

 

 

CG

 

 

SUPPLY

B

COMPRESSOR

D

 

 

X

 

Corner & Center of Gravity Locations

Model

X

Y

Shipping

Operating

 

Corner Weights ( lbs )

 

(in)

(in)

Weight

Weight

 

 

 

 

 

 

A

 

B

C

 

D

 

(lbs)

(lbs)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPG036045*

37

30

550

525

100

 

165

100

 

165

 

 

 

 

 

 

 

 

 

 

 

CPG036090*

37

30

560

535

100

 

170

100

 

170

 

 

 

 

 

 

 

 

 

 

 

CPG048090*

37

30

600

575

110

 

180

110

 

180

 

 

 

 

 

 

 

 

 

 

 

CPG048115*

37

30

605

580

110

 

180

110

 

180

 

 

 

 

 

 

 

 

 

 

 

CPG060090*

37

30

645

620

115

 

190

120

 

195

 

 

 

 

 

 

 

 

 

 

 

CPG060140*

37

30

655

630

120

 

195

120

 

195

 

 

 

 

 

 

 

 

 

 

 

CPG072140*

37

30

715

690

130

 

215

130

 

215

 

 

 

 

 

 

 

 

 

 

 

* Weights shown are belt drive with no accessories.

CAUTION

TO PREVENT SEVERE DAMAGE TO THE BOTTOM OF THE UNIT, DO NOT

FORK LIFT UNIT AFTER WOOD STRUTS HAVE BEEN REMOVED.

Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, care should be taken to center the unit. Check for proper alignment and orientation of supply and return openings with duct.

RIGGING REMOVAL

CAUTION

TO PREVENT DAMAGE TO THE UNIT, DO NOT ALLOW CRANE HOOKS

AND SPREADER BARS TO REST ON THE ROOF OF THE UNIT.

Remove spreader bars, lifting cables and other rigging equipment.

8