![Installation of Water WizardTM (optional)](/images/new-backgrounds/67540/6754023x1.webp)
Installation of Water WizardTM (optional)
Evaporative Cooling with the Water Wizard™
Note
The following instructions are provided for evaporative coolers equipped with the Water Wizard™ only. Additional instructions are provided for evaporative coolers equipped with the
Warning
Disconnect and
Water Wizard™ Valves
(When provided by Greenheck)
Unit | Assembly | GFC | ASCO | Solenoid | De- |
|
|
Model | Number | Part | Part No. | Type | Energized | Diameter | Qty. |
|
| No. |
|
| Position |
|
|
|
|
|
|
|
|
|
|
MSX - |
| 461262 | 8210G2 | Supply | Closed | 1/2 inch | 1 |
| (12.7 mm) | ||||||
H12/H22 |
| ||||||
MSX - H32 | 852370 |
|
| Supply |
| 1/2 inch |
|
| 383086 | 8210G34 | Line | Open | 1 | ||
| (12.7 mm) | ||||||
(<9000 cfm) |
| ||||||
|
|
|
| Drain |
|
|
|
MSX - H32 |
| 383088 | 8210G9 | Supply | Closed | 3/4 inch | 1 |
| (19.05 mm) | ||||||
(≥9000 cfm) | 852371 |
|
|
|
|
|
|
|
| Supply |
| 1/2 inch |
| ||
| 383086 | 8210G34 | Line | Open | 1 | ||
H38, H42 |
| (12.7 mm) | |||||
|
|
|
| Drain |
|
|
|
Part numbers subject to change.
1.Install Normally Closed Supply Line/ Solenoid
Connect the water supply line to the manual supply valve in the unit. Install the supply solenoid in the supply line, upstream of the manual supply valve and below the roof line.
2.Install Normally Open Drain Line/ Solenoid
Connect the drain line to the supply line between the manual supply valve and the supply solenoid. Install a drain solenoid in the drain line, below the roof line. A trap should be installed in the drain line.
Note
Solenoid(s) may be provided by Greenheck (if ordered) or by others.
Caution
Any wiring deviations may result in personal injury or property damage. Greenheck is not responsible for any damage to, or failure of the unit caused by incorrect final wiring.
To Media
| Pressure | Factory |
| Gauge | |
| Installed | |
| Sump Drain | |
|
| |
| Manual Supply |
|
| Valve |
|
Roof | Supply Solenoid | |
Line | (Normally Closed) | |
Trap | Supply Line Drain Solenoid | Field |
| (Normally Open) | Installed |
Water Wizard™ Installation
3. Wire the Solenoid(s)
Wire the supply line solenoid and drain solenoid as shown on the unit’s wiring diagram in the control center.
4. Wire the Temperature Sensor
If the evaporative cooler shipped separate from the unit, the temperature sensor must be wired. The sensor wire is bundled inside the discharge end of the evaporative cooler. Wire the sensor wire to terminals AI2 and AIC on the terminal strip in the unit’s control center.
Note
The Water Wizard™
12 | Model MSX | ® |