Greenheck Fan 470658 MSX manual Operation - WaterWizard optional, Drain Mode, Flow Test Mode

Models: 470658 MSX

1 40
Download 40 pages 6.86 Kb
Page 25
Image 25
Operation - Water Wizard™ (optional)

Operation - Water Wizard™ (optional)

L1

L2

L3

Function Key

 

Up Key

Enter Key

 

Down Key

Water Wizard™ User Interface

Key Function Description

Drain Mode

Drain Mode locks open the drain solenoid and drains the supply line between the supply solenoid and the media. To activate Drain Mode simultaneously, press the Function and Enter Keys (L2 will light). To deactivate Drain Mode and unlock the drain solenoid, simultaneously press the Function and Enter Keys again.

Flow Test Mode

Activating Flow Test Mode opens the supply solenoid and allows water to pass to the manual supply valve. To activate Flow Test Mode, press and hold the Function Key for one second (L3 will flash). To deactivate Flow Test Mode and allow the supply solenoid to close, press and hold the Function Key again for one second.

Caution

The sump drain line must be clear and draining to a safe location before using Flow Test Mode.

Caution

Be aware of the water level in the sump tank at all times when using the Flow Test Mode.

Program Mode

Program Mode allows the user to view the Program Menu and edit the factory default settings. To access Program Mode and view the Program Menu press and hold the Enter key for three seconds. While viewing the Program Menu press the Up and Down keys to scroll through the Menu Options. To view the setting of the selected Menu Option, press the Enter key.

To edit the setting, press the Up or Down key while viewing the setting. To save the setting and return to the Program Menu, press the Enter key. To return to the Program Menu without saving the change, wait

10 seconds. To exit Program Mode from the Program Menu, wait 10 seconds.

warning

Changing the default settings will significantly affect performance. Only change a setting after reading and understanding this entire manual.

warning

The Enter key must be pressed to save any changes made to a setting.

Dry Bulb Temperature

The dry bulb temperature is visible on the home screen. If a number is not visible, wait 15 seconds and use the Up and Down Keys until a number is displayed.

Wet Bulb Temperature

To view the Wet Bulb Temperature, simultaneously press and hold the Up and Down Keys.

Indicating Lights

Three indicating lights are located across the top of the display to indicate the status of the Water Wizard™.

Light Status

Indicating

 

 

Blinking

Blinking

On

Off

(Long on,

(Short on,

Light

 

 

Short Off)

Long Off)

 

 

 

 

 

 

Call for

 

L1

Call for

No call

cooling.

 

for

Outdoor

N/A

cooling

 

cooling

temperature

 

 

 

 

 

 

 

lockout.

 

 

 

 

 

 

 

 

 

 

Supply

 

Drain

Drain

 

solenoid

L2

 

open.

solenoid

solenoid

N/A

(Drain

 

open

closed

 

 

 

solenoid

 

 

 

 

 

 

 

 

closed).

 

 

 

 

 

 

 

 

Supply

 

L3

Cooling

Cooling

solenoid

Flow test

on

off

locked

mode active

 

 

 

 

closed

 

 

 

 

 

 

®

Model MSX Make-Up Air

25

Page 25
Image 25