Greenheck Fan 470658 MSX Cooling Coils, Chilled Water Coils, Maintenance - Routine continued

Models: 470658 MSX

1 40
Download 40 pages 6.86 Kb
Page 35
Image 35
Cooling Coils

Maintenance - Routine continued

Cooling Coils

warning

Repair and replacement of the coil and the connecting piping, valves, etc., should be performed by a qualified individual.

Inspect the coil for signs of corrosion and/or leaks. Repair any leaks as required.

Inspect the coil’s surface for foreign material. If the coil surface needs cleaning, clean the coil from the leaving air-side so that foreign material will be washed out of the coil rather than pushed farther in.

Inspect and clean the drain pan to prevent the growth of algae and other organisms.

important

Be sure to read and follow the manufacturer’s recommendations before using any cleaning fluid.

caution

Caution should be used to avoid injury when venting the coil. High pressure and/or high temperature fluids can cause serious injuries.

Chilled Water Coils

Test the circulating fluid for sediment, corrosive products and biological contaminants. Make the necessary corrective measures.

Maintain adequate fluid velocities and proper filtering of the fluid.

If automatic air vents are not utilized, periodic venting of the coil is recommended to remove accumulated air.

®