Greenheck Fan 470658 MSX Mount Pressure Tap, Run Pressure Tap Lines, Set the Building Pressure

Models: 470658 MSX

1 40
Download 40 pages 6.86 Kb
Page 15
Image 15
1. Mount Pressure Tap

Installation of Building Pressure Control (optional)

1. Mount Pressure Tap

Using the factory provided bracket, mount the pressure tap to the

outside of the unit. Choose a location out of the prevailing winds and away from supply or exhaust fans to assure accurate readings.

2. Run Pressure Tap Lines

Run a pressure tap line from the pressure tap on the outside of the unit to the low pressure tap on the back of the photohelic gauge. Run a second pressure tap line from the high pressure tap on the back of the photohelic gauge to the space. Fifty feet of tubing is supplied with the unit.

Factory

 

 

 

High Pressure

 

 

 

 

 

 

Tap

Wiring

 

 

 

to Space

Low Pressure

Tap

to Outside

Connections for Photohelic Gauge

3. Set the Building Pressure

The pressure gauge is used to set the desired building pressure. The pressure is set by adjusting the knobs for the upper and lower pressure limits. Typical settings are 0.0 inch wc for the lower and 0.10 inch wc for the upper pressure setting.

Pressure Indicating

Pressure Setting

Needle

Needles

Pressure Setting Knobs

Typical Photohelic Gauge Settings

®

Model MSX Make-Up Air