Optional Accessories
Remote Control Panel
The remote panel is a series of junction boxes ganged together and includes a stainless steel face plate. The remote panel is available with a number of different alarm lights and switches to control the unit. The remote panel ships loose and requires mounting and wiring in the field. Refer to “Remote Panel Wiring Schematics” (Part #461368) for instructions on wiring the remote panel to the 24 VAC terminal strip in the energy recovery unit control center.
The remote panel is available with the following options:
1)Unit on/off switch
2)Unit on/off light
3)
4)Hand/off/auto switch
5)Time delay override
6)Exhaust air dirty filter light
7)Outdoor air dirty filter light
8)Economizer light
9)Frost control light
10)Wheel rotation sensor light
Variable Frequency Drive for Energy Recovery Wheel
Factory installed VFD for the energy recovery wheel are programmed at the factory per the settings shown in TABLE 4 below. Refer to the instruction manual that ships with the unit when making adjustments. A copy of the manual can be found online at www.drives.com. For technical support, contact Yaskawa direct at
| Parameters | Setting | Comment |
|
|
|
|
|
|
n01 | Access Level | 1 | n01 - n79 can be read or set |
|
|
|
|
|
|
n02 | Operation Method | 1 | Terminal |
|
|
|
|
|
|
n03 | Reference Selection | 2 |
| |
|
|
|
|
|
n09 | Max Frequency | 60 Hz |
|
|
|
|
|
|
|
n16 | Accl Time 1 | 10 | Seconds |
|
|
|
|
|
|
n17 | Decel Time 2 | 10 | Seconds | VFD key pad & LCD |
|
|
|
| |
n29 | Jog Frequency | 6 Hz |
| |
|
| |||
|
|
|
|
|
n30 | Ref Upper Limit | 100% | % of n09 |
|
|
|
|
|
|
n31 | Ref Lower Limit | 0% | % of n09 |
|
|
|
|
|
|
n32 | Motor Rated FLA | ? A |
|
|
|
|
|
|
|
n36 | 10 |
|
| |
|
|
|
|
|
n40 | Frequency Detection | 4 |
|
|
|
|
|
|
|
n41 | Analog Freq. Ref. Gain | 0 | Inverse acting |
|
|
|
|
|
|
n42 | Analog Freq. Ref. Bias | 99 | Inverse acting |
|
|
|
|
|
|
n58 | Freq. Dectection Level | 5.9 Hz |
|
|
|
|
|
|
|
n01 | Access Level | 0 | n01 read or set; |
|
|
|
|
|
|
TABLE 4: Factory settings for VFD used on energy recovery wheel