Water Coils

Installation

Coil Application Recommendations

Factory installed cooling and heating components are mounted in the coil section of the unit. The coil section is downstream of the energy wheel on the supply air side of the unit.

See FIGURE 10 for coil connection location. Coil connections are located external to the unit as shown. Coil connections that are not external have been ordered from the factory with interior or exhaust airstream coil connections.

Note: DX coil liquid connections are accessible through access doors shown in FIGURE 10.

Water coil connections

DX coil liquid connection access door

Water Coils

1.Piping should be in accordance with accepted industry standards. Pipework should be supported independently of the coils. Water connections are male N.P.T iron pipe. When installing couplings, do not apply undue stress to the connection extending through the unit. Use a backup pipe wrench to avoid breaking the weld between coil connection and header.

Water coil connections

FIGURE 10

2.Connect the WATER SUPPLY TO THE BOTTOM CONNECTION on the air leaving side and the WATER RETURN TO THE TOP CONNECTION on the air entering side. To ensure proper venting, an external air vent in the piping is recommended. Connecting the supply and/or return in any other manner will result in very poor performance. Be sure to replace factory installed grommets around coil connections if removed for piping. Failure to replace grommets will result in water leakage into the unit and altered performance.

3.The air vent at the uppermost point should be temporarily opened during system start-up to release all of the air from the coil. To maintain heat transfer capacity, periodically vent any air in coil.

4.Water coils are not normally recommended for use with entering air temperatures below 40oF; however, the energy recovery wheel maintains a pre-coil temperature higher than 40oF. No control system can be depended on to be 100% safe against freeze-up with water coils. Glycol solutions or brines are the only safe media for operation of water coils with low entering air temperatures.

CONTINUOUS WATER CIRCULATION THROUGH THE COIL AT ALL TIMES IS HIGHLY RECOMMENDED.

5.Pipe sizes for the system must be selected on the basis of the head (pressure) available from the circulation pump. The velocity should not exceed 6 feet per second and the friction loss should be approximately

3 feet of water column per 100 feet of pipe.

6.For chilled water coils, the condensate drain pipe should be sized adequately to ensure the condensate drains properly. See Drain Pan Traps and FIGURE 11.

Direct Expansion (DX) Coils

1.Piping should be in accordance with accepted industry standards. Pipework should be supported independently of the coils. Undue stress should not be applied at the connection to coil headers.

2.The condensate drain pipe should be sized adequately to ensure the condensate drains properly. See Drain Pan Traps and FIGURE 11.

3.When connecting suction and liquid connections make sure the coil is free from all foreign material. Make sure all joints are tight and free of leakage. Be sure to replace factory installed grommets around coil connections if removed for piping.

4.Greenheck does not supply condensing units; for further instruction on DX coil installation and operation contact your condensing unit manufacturer.