Service Clearances / Access Locations

Installation

Service Clearances / Access Locations

APEX-200 units require minimum clearances for access on all sides for routine maintenance. Filter replacement, drain pan inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and belt adjustment, are examples of routine maintenance that must be performed. Blower and motor assemblies, energy recovery wheel cassettes, coil and filter sections are always provided with a service door or panel for proper component access. Clearances for component removal may be greater than the service clearances. Contact Greenheck for component removal clearance.

Exhaust

Hood

36 in.

Outdoor Air

Intake Hood

96 in. 29 in.36 in.

 

 

Exhaust

Coil

96 in.

2 in.

Wheel Cassettes

Air

Filters

Inlet

Section

 

Control

 

 

 

36 in.

Exhaust

Center

 

 

 

 

 

Hood

 

 

 

 

 

 

FIGURE 8: Clearances for service on APEX-200

 

 

 

Dimensional Data / Access Door Descriptions

Model

 

 

 

Exterior Dimensions

 

 

 

A

B

C

 

D

E

F

G

H*

I*

 

 

APEX-200

287.75

96.5

92.5

 

58.75

15.75

31

10.75

24.63

25.125

 

 

 

 

 

 

 

 

 

 

 

Width (just unit):

96.5

Width (including lifting lugs):

99.875

Overall Width (with exhaust hoods):

146.75

Overall Length (with outdoor air hood):

303.5

(All dimensions shown are in inches.)

 

4

 

 

2

3

5

C

 

 

E

 

 

 

1

 

7

 

 

8

6

 

 

 

 

D

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

 

F

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

G

* G, H, & I typical both sides of unit

 

 

 

 

 

FIGURE 9: Dimensional data and access door locations.

7

Following is a list of items accessible through the access doors shown on the diagram at the left. Some items are optional and may not have been provided.

1)Exhaust blower #1, energy recovery wheel #1 maintenance (segment removal for cleaning)

2)Half of supply filters

3)Exhaust filters (refer to Filter Maintenance). Energy recovery wheel motors, belts, and seals

4)Supply blower, motor, and drives

5)Supply blower and drives

6)Coil drain pan and electric heater

7)Control center, variable frequency drives, and temperature control package

8)Half of supply filters

9)Exhaust blower #2, energy recovery wheel #2 maintenance (segment removal for cleaning)

10)Outdoor air damper, electric preheater, frost control sensors, and economizer sensors

11)Aluminum mesh filters (both sides of hood)

®