Greenheck Fan APEX-200 Unit Weights dry weights, Recommended Roof Openings, Roof Curb Mounting

Models: APEX-200

1 28
Download 28 pages 63.53 Kb
Page 4
Image 4
Unit Weights (dry weights)

Installation

Unit Weights (dry weights)

 

Unit

Approx. Weight (lbs)

APEX-200

(without coils)

9,000

APEX-200

(with HW & CW coils)

12,000

 

 

 

Recommended Roof Openings

W

Exhaust

 

Outdoor

A

Air

 

 

Air

 

Intake

 

 

 

 

Discharge

 

 

 

 

 

 

D

C

B

2.50

 

 

 

 

From Inside Curb

L

To Recommended

 

FIGURE 2: Recommended roof openings.

Roof Opening

 

Model

 

A

B

C

D

APEX-200

86

44

 

68.75

44

All dimensions shown are in inches.

 

 

 

 

 

 

 

 

Curb Outside Dimensions

 

 

 

 

 

 

 

 

Model

 

L

W

 

 

APEX-200

 

283.5

92.0

 

 

Dimensions shown are in inches.

Roof Curb Mounting

Rooftop units require curbs to be mounted first. The duct connections must be located so they will be clear of structural members of the building.

1.Factory Supplied Roof Curbs

Roof curbs are Model GKD, which are shipped in a knockdown kit and require field assembly (by others). Assembly instructions are included with the curb.

2.Cut Roof Opening and Locate Curb

Layout the unit roof openings such that the supply discharge & exhaust inlet of the unit will line up with the corresponding ductwork (refer to Recommended Roof Openings). Do not make openings larger than necessary. Be sure to allow for the recommended service clearances. Keep the supply inlet of the unit away from any other exhaust fans. Likewise, position the exhaust discharge opening away from fresh air intakes of any other equipment.

3.Install Curb

Locate curb over roof opening and fasten in place. Check that the diagonal dimensions are within ±18 inch of each other and adjust as necessary. Shim as required to level.

4.Set the Unit

Lift unit to a point directly above the curb and duct openings. Guide unit while lowering to align with duct openings. Roof curbs fit inside the unit base. Make sure the unit is properly seated on the curb and is level.

5.Duct Work

Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines.

Duct Size:

80 in. x 30 in.

FIGURE 3: Duct dimensions.

SIDE OF UNIT

BASE

2.00 UnitApprox. Weight (lbs)Recommended Roof OpeningsFIGURE 2: Recommended roof openings.

6.00

2.002 IN. INSULATION

1.25ModelCurb Outside DimensionsRoof Curb Mounting1.Factory Supplied Roof Curbs2.Cut Roof Opening and Locate Curb3.Install Curb

0.754.Set the Unit5.Duct WorkManual background

ROOF CURB

FIGURE 4: Roof curb details.

Dimensions based on Greenheck-supplied roof curb only!

4®

Page 4