ACCESSING ENERGY RECOVERY WHEEL

Routine Maintenance

Energy Recovery Wheel Maintenance

Annual inspection of the energy recovery wheel is recommended. Units ventilating smoking lounges and other non-clean air spaces should have energy recovery wheel inspections more often based upon need. Inspections for smoke ventilation applications are recommended bimonthly to quarterly until a regular schedule can be established.

ACCESSING ENERGY RECOVERY WHEEL

The APEX has two energy recovery wheels. Open the exhaust blower access doors to access each wheel (FIGURE 26). The energy recovery wheel cassettes do not slide out due to their size and weight.

**WARNING: Disconnect power to the unit before performing any type of service.**

FIGURE 26: Access to wheel through exhaust blower door.

REMOVING THE ENERGY RECOVERY WHEEL SEGMENTS

Bracket Segment Retainer

Steel retainers are located on

 

 

the inside of the wheel rim

Lift Away

 

From Segment

 

(FIGURE 27). Push the retainer

Catch-

 

toward center of wheel, then

Segment Retainer

 

 

 

lift up and away to release

 

 

segments (FIGURE 28 & 29).

 

 

 

Push Toward Center

 

 

FIGURE 27: Wheel retaining arms.

IMPORTANT! PLACE RETAINERS BACK IN THE ORIGINAL POSITION BEFORE ROTATING THE ENERGY RECOVERY WHEEL. OTHERWISE DAMAGE TO RETAINER WILL OCCUR.

Inside of Wheel Rim

Spoke

FIGURE 28: Wheel segment retaining arms

FIGURE 29: Wheel segment removed to

rotated for removal.

allow for cleaning.

 

 