7.Verify that both airflow and system static pressure are in agreement with the specifications.. If these conditions are met, check for water carry over from the discharge side of the media.. If carry over is observed, check the distribution header for holes or tears and the water standoff tube for blockage..
8.After all final adjustments are made, remove the jumper wires, connect “call for cooling” signal, and replace all access panels.. The unit is now ready for operation..
Overflow | Pump | Supply | Float | ||
Valve | Filter | Connection | Valve | ||
|
Threaded
Float
Adjustment
Water Flow Adjustment DevicePump and Float Components
HRE WATER SUPPLY CONNECTION LOCATION
Model |
| Water Supply Connection Locations |
| ||
|
|
|
| ||
A | B | C | D | ||
| |||||
|
|
|
|
| |
37..375 | 4..625 | 4..625 | 39..25 | ||
|
|
|
|
| |
38..75 | 4..625 | 4..625 | 43..00 | ||
|
|
|
|
| |
43..50 | 4..625 | 4..625 | 46..125 | ||
|
|
|
|
| |
43..50 | 4..625 | 4..625 | 52..625 | ||
|
|
|
|
|
Dimensions from outside of unit (in inches)
D
C
Ø 0.875
Run 1/4 inch line up through 7/8 inch hole here and bring around end
of sump to supply connection.
1/4 inch Water Supply Connection
Top View
OA INLET
1/4 inch Water Supply Connection
Ø 0.875
Run 1/4 inch line up through 7/8 inch hole here and bring around end of sump to supply connection.
EA INLET
B
A
11