HRE WATER SUPPLY CONNECTION LOCATION

7.Verify that both airflow and system static pressure are in agreement with the specifications.. If these conditions are met, check for water carry over from the discharge side of the media.. If carry over is observed, check the distribution header for holes or tears and the water standoff tube for blockage..

8.After all final adjustments are made, remove the jumper wires, connect “call for cooling” signal, and replace all access panels.. The unit is now ready for operation..

Overflow

Bleed-Off

Pump

Supply

Float

Valve

Filter

Connection

Valve

 

Threaded

Float

Adjustment

Water Flow Adjustment DevicePump and Float Components

HRE WATER SUPPLY CONNECTION LOCATION

Model

 

Water Supply Connection Locations

 

 

 

 

 

A

B

C

D

 

 

 

 

 

 

HRE-20

37..375

4..625

4..625

39..25

 

 

 

 

 

HRE-45

38..75

4..625

4..625

43..00

 

 

 

 

 

HRE-55

43..50

4..625

4..625

46..125

 

 

 

 

 

HRE-90

43..50

4..625

4..625

52..625

 

 

 

 

 

Dimensions from outside of unit (in inches)

D

C

Ø 0.875

Run 1/4 inch line up through 7/8 inch hole here and bring around end

of sump to supply connection.

1/4 inch Water Supply Connection

Top View

OA INLET Top ViewManual background

1/4 inch Water Supply Connection

Ø 0.875

Run 1/4 inch line up through 7/8 inch hole here and bring around end of sump to supply connection.

EA INLET

B

A

11

Page 11
Image 11