RAIL MOUNTING
Rail Layout
•Rails designed to handle the weight of the HRE should be positioned as shown on the diagram (rails by others)..
•Make sure that rail positioning does not interfere with the supply air discharge opening or the exhaust air intake opening on the HRE unit.. Avoid area dimensioned “B” below
•Rails should run the width of the unit and extend beyond the unit a minimum of 12 inches on each side..
•Set unit on rails.
OUTDOOR
AIR
INTAKE
HOOD
SUPPLY/EXHAUST
OPENING
B A
Side view of HRE on rails
Isometric view of HRE on rails
Model | Rail Mounting | ||
|
| ||
A | B | ||
| |||
|
|
| |
5..1 | 25..0 | ||
|
|
| |
7..1 | 25..1 | ||
|
|
| |
5..7 | 35..0 | ||
|
|
| |
6..6 | 36..1 | ||
|
|
|
All dimensions shown are in inches..
DUCTWORK CONNECTIONS
Examples of good and poor
R
|
| tion |
| a | |
t |
| |
o |
|
|
Length of Straight Duct
R
|
| tion |
| a | |
t |
| |
o |
|
|
GOOD
POOR
Recommended Discharge Duct Size and Length
HRE Model | HRE Blower Size | Duct Size | Straight Duct Length |
|
|
|
|
10 | 14 x 14 | 40 | |
|
|
|
|
12 | 20 x 20 | 48 | |
|
|
|
|
15 | 28 x 28 | 60 | |
|
|
|
|
18 | 32 x 32 | 72 | |
|
|
|
|
Dimensions shown are in inches..
SUPPLY WEATHERHOOD
Supply weatherhood will be factory mounted..
EXHAUST WEATHERHOOD
The exhaust weatherhood is shipped separately as a kit with its own instructions..
Dampers
Backdraft dampers are always included as an integral part of the exhaust hood assemblies.. Motorized outdoor air and exhaust air dampers are optional and are factory mounted (and wired) at the inlet..